Sample Record for 2021-11-12-40

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 215601 DEA: 024H3404 EFIS: 0218000109 QA Service Level: 1
DIST-CO-RTE-PM: 02-TRI-299-5.2/5.7
Work Description: INSTALL LEFT TURN LANE.
Location Description: TRINITY COUNTY NEAR SALYER FROM 0.3 MILE WEST OF DENNY ROAD TO 0.2 MILE WEST OF PONY BAR CREEK BRIDGE
Contractor Name: MERCER-FRASER COMPANY
Contractor Address: 77 2nd St, Eureka, CA 95501
Resident Engineer: Joel Gasik Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2021-11-12-40
TL Number from the TL Form: 695661
Sample Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Sample Organization Contact: (916) 227-7302
Type of Sample: Acceptance
Type of Material: Asphalt Binder
Sample Taken Date: 11/12/2021
Date that the sample was received by the laboratory/organization performing the testing: 12/02/2021
The quantity of what the sample constitutes: 1 CAN
A brief description of the sample: BINDER
From where was the sample collected: Source
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Valero - Benicia, CA

Material Information

Performance Grade: PG 64-28 M
Modified: Yes
Lot number:
Sublot number:
Tank number:
Time of sample:
HMA Supplier: Mercer Fraser - Willowcreek
Certified Asphalt Supplier: Valero Marketing & Supply - Benicia CA
Multigrade: No
Multigrade Type:
Asphalt Binder Mix Number:

Test Results

Test 1 of 4

DIME Test ID: 2021-11-12-40-1
Test Method: AASHTO T315-20: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 12/13/2021
Date Tested: 12/08/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications OG
Test Result Compliance: complies
Additional Comments When Verified:
Phase Original binder
Test Plate Diameter 25 mm
Test Gap 1 mm
Test Frequency 10.0 rad/s
Strain Amplitude 12.00 %
Stress Amplitude 0.185 kPa
Phase Angle (δ) (for the 10 cycles) 64.9 degree
Complex Modulus (G*) (for the 10 measurements) 1.538 kPa
Test Temperature (Specimen 1) 64.0 C
Dynamic Shear, G*/sin(δ) 1.70 kPa

Test 2 of 4

DIME Test ID: 2021-11-12-40-2
Test Method: AASHTO T315-20: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 12/13/2021
Date Tested: 12/08/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications RTFO
Test Result Compliance: complies
Additional Comments When Verified:
Phase RTFO residue two specimens
Test Plate Diameter 25 mm
Test Gap 1 mm
Test Frequency 10.0 rad/s
Strain Amplitude 10.00 %
Stress Amplitude 0.431 kPa
Phase Angle (δ) (for the 10 cycles) 58.8 degree
Complex Modulus (G*) (for the 10 measurements) 4.313 kPa
Test Temperature (Specimen 1) 64.0 C
Dynamic Shear, G*/sin(δ) 5.04 kPa
Stress Amplitude 2 0.255 kPa
Phase Angle 2 (δ) (for the 10 cycles) 60.4 degree
Complex Modulus 2 (G*) (for the 10 measurements) 2.548 kPa
Test Temperature (Specimen 2) 70.0 C
Dynamic Shear 2, G*/sin(δ) 2.93 kPa
Delta at 2.2 kpa 61.0 degree

Test 3 of 4

DIME Test ID: 2021-11-12-40-3
Test Method: AASHTO T315-20: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 12/13/2021
Date Tested: 12/10/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications PAV
Test Result Compliance: complies
Additional Comments When Verified:
Phase PAV residue
Test Plate Diameter 8 mm
Test Gap 2 mm
Test Frequency 10.0 rad/s
Strain Amplitude 1.00 %
Stress Amplitude 15.459 kPa
Phase Angle (δ) (for the 10 cycles) 43.4 degree
Complex Modulus (G*) (for the 10 measurements) 1545.899 kPa
Test Temperature (Specimen 1) 22.0 C
(G*) x sin(δ)= 1062 kPa

Test 4 of 4

DIME Test ID: 2021-11-12-40-5
Test Method: AASHTO T313-19: Standard Method of Test for Determining the Flexural Creep Stiffness of Asphalt Binder Using the Bending Beam Rheometer (BBR)
Verified Date: 12/13/2021
Date Tested: 12/13/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: per 2018 standard specification
Test Result Compliance: complies
Additional Comments When Verified:
Minimum test bath temperature at 240 s -18.0 C
Maximum test bath temperature at 240 s -18.0 C
Time of test load application no data HH:MM:SS
File name of test data no data
Time beam in bath no data
Time test started no data HH:MM:SS
Flags issued by software during test no data
Correlation coefficient (R²) 0
Regression coefficient a no data
Regression coefficient b no data
Regression coefficient c no data
Load at time 0.0 0.0 mN
Deflection at time 0.0 s 0.000 µm
Load at time 0.5 s 0.0 mN
Deflection at time 0.5 s 0.000 µm
Load at 60.0 s 1039.0 mN
Beam deflection 60.0 s 1.371 µm
Measured Stiffness Modulus 60.0 s 61.100 mPa
Estimated Stiffness Modulus 60.0 s 61.100 mPa
Difference between stiffness moduli 60.0 s no data
Estimated m-value 60.0 s 0.343