Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 8801 DEA: AML-CEM EFIS: AML-CEM
QA Service Level:
DIST-CO-RTE-PM: 59---
Work Description: Special project for Cementitious Materials for use in Concrete Authorized Material List (AML)
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown
DIME Sample ID: 2021-11-09-22
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Sample Organization Contact: (916) 227-7071
Type of Sample: Annual Source Testing
Type of Material: Cementitious
Sample Taken Date: 11/09/2021
Date that the sample was received by the laboratory/organization performing the testing: 11/09/2021
The quantity of what the sample constitutes: 1 Bucket
A brief description of the sample: Type II/IV Portland Cement
From where was the sample collected: Source
Laboratory sample identification: CM215180
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Pan Pacific
DIME Test ID: 2021-11-09-22-2
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 01/07/2022
Date Tested: 12/02/2021
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: Specimen 3 was eliminated from the average for being outside allowable limits per Section 12 of ASTM C109
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no
|
Age of specimen
|
3 days
|
The amount of flow
|
110 %
|
The amount of water used
|
48.5 %
|
Compressive strength of 1st specimen
|
3328 psi
|
Compressive strength of 2nd specimen
|
3512 psi
|
Compressive strength of 3rd specimen
|
3122 psi
|
Average Compressive strength (to nearest 10 psi)
|
3420 psi
|
DIME Test ID: 2021-11-09-22-3
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 01/07/2022
Date Tested: 12/06/2021
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: Specimen 1 was eliminated from the average for being outside allowable limits per Section 12 of ASTM C109
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no
|
Age of specimen
|
7 days
|
The amount of flow
|
110 %
|
The amount of water used
|
48.5 %
|
Compressive strength of 1st specimen
|
3328 psi
|
Compressive strength of 2nd specimen
|
4542 psi
|
Compressive strength of 3rd specimen
|
4223 psi
|
Average Compressive strength (to nearest 10 psi)
|
4380 psi
|
DIME Test ID: 2021-11-09-22-4
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 01/07/2022
Date Tested: 12/27/2021
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: Specimen 3 was eliminated from the average for being outside allowable limits per Section 12 of ASTM C109
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no
|
Age of specimen
|
28 days
|
The amount of flow
|
110 %
|
The amount of water used
|
48.5 %
|
Compressive strength of 1st specimen
|
5617 psi
|
Compressive strength of 2nd specimen
|
5587 psi
|
Compressive strength of 3rd specimen
|
5105 psi
|
Average Compressive strength (to nearest 10 psi)
|
5600 psi
|
DIME Test ID: 2021-11-09-22-5
Test Method: ASTM C185-15a: Standard Test Method for Air Content of Hydraulic Cement Mortar
Verified Date: 01/07/2022
Date Tested: 11/09/2021
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Specific gravity
|
3.15
|
Water Content
|
240
|
The amount of flow (In percent)
|
89 %
|
The amount of water used (In percent)
|
68.57 %
|
Net Weight of Sample
|
847.9 grams
|
Air Content
|
6 %
|
DIME Test ID: 2021-11-09-22-6
Test Method: ASTM C191-13: Standard Test Methods for Time of Setting of Hydraulic Cement by Vicat Needle
Verified Date: 01/07/2022
Date Tested: 11/19/2021
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Type of Water Used
|
Type IV grade reagent water
|
Initial time of setting
|
241 min
|
Final time of setting
|
no data
|
DIME Test ID: 2021-11-09-22-7
Test Method: ASTM C204-11: Standard Test Methods for Fineness of Hydraulic Cement by Air-Permeability Apparatus
Verified Date: 01/07/2022
Date Tested: 12/13/2021
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Method Used
|
Test Method A
|
Test Time
|
111 seconds
|
Fineness
|
4182 cm^2/g
|
DIME Test ID: 2021-11-09-22-8
Test Method: ASTM C187-16: Standard Test Method for Amount of Water Required for Normal Consistency of Hydraulic Cement Paste (Water Normal Consistency)
Verified Date: 01/07/2022
Date Tested: 11/19/2021
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Mass of Water
|
172 g
|
Mass of Dry Cement
|
650 g
|
Water required for normal consistency
|
26.5 %
|