Print Report | Back to Sample Detail

Sample Record for 2021-10-26-6

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 993322 DEA: 010L4204 EFIS: 0122000008 QA Service Level: 1
DIST-CO-RTE-PM: 01-MEN,MEN/MEN-101-4/6, 4.0/6.0
Work Description: Landslide Repair near Commisky
Location Description:
Contractor Name: MALCOLM DRILLING COMPANY, INC.
Contractor Address: 246 GHILOTTI AVENUE, SANTA ROSA, CA 95407
Resident Engineer: Katharine Perrin Structure Rep.: Kitt Tongthaworn

Sample Information

DIME Sample ID: 2021-10-26-6
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Bay Area Field Office
Sample Organization Contact: (916) 284-6784
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Welded Hoops
Sample Taken Date: 10/26/2021
Date that the sample was received by the laboratory/organization performing the testing: 10/28/2021
The quantity of what the sample constitutes: 4 welded hoops
A brief description of the sample: Flash Welded Rebar Hoops
From where was the sample collected: Supplier
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Conco Reinforcing

Material Information

Production or Authorization Testing: Authorization Testing
Service or Ultimate: Service
Rebar Heat Number(s): 350021157
Hoop Manufacturer Lot Number(s): H11
Material Standard Code: ASTM A615
Material Grade: 60
Rebar Size: #8
Diameter of Hoop: 5'-6"
Epoxy Coated: No
Epoxy Coating Color: NA
Rebar Manufacturer: Nucor
Welding Company: TNT Rebar
Coating Standards: Uncoated
Weld Type: Flash Welded

Test Results

Test 1 of 3

DIME Test ID: 2021-10-26-6-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 11/01/2021
Date Tested: 10/29/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 1
SampleMfg. Lot Number(s)SizeArea (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
1H118/25mm0.7977760.6498431Ok Neckingbewing
UTM 400kip
Temperature 72 f

Test 2 of 3

DIME Test ID: 2021-10-26-6-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 11/01/2021
Date Tested: 10/29/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 1
SampleMfg. Lot Number(s)SizeArea (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
2H118/25mm0.7978397.9799238Ok Neckingbewing
UTM 400kip
Temperature 72 f

Test 3 of 3

DIME Test ID: 2021-10-26-6-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 11/01/2021
Date Tested: 10/29/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 1
SampleMfg. Lot Number(s)SizeArea (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
3H118/25mm0.7978042.6398788Ok Neckingbewing
UTM 400kip
Temperature 72 f