Project Information

Project ID: 213521 DEA: 050L7234 EFIS: 0515000099 QA Service Level: 1
DIST-CO-RTE-PM: 05-SLO-58-3.08
Work Description: TROUT CREEK BRIDGE REPLACEMENT
Location Description: IN SAN LUIS OBISPO COUNTY ON HWY 58 EAST OF SANTA MARGARITA AT TROUT CREEK BRIDGE (BR NO. 49-0091).
Contractor Name: SOUZA CONSTRUCTION
Contractor Address: 4027 Santa Fe Road, San Luis Obispo, CA 93403
Resident Engineer: Thomas Petersen Structure Rep.: Salvador Heredia

Sample Information

DIME Sample ID: 2021-10-20-21
TL Number from the TL Form: C918914
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (530) 329-6527
Type of Sample: Quality Assurance
Type of Material: SMTL TM3 - Fastener Assembly
Sample Taken Date: 10/20/2021
Date that the sample was received by the laboratory/organization performing the testing: 10/20/2021
The quantity of what the sample constitutes: 1
A brief description of the sample: A449 ATR with Coupling Nut
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: BSMI

Material Information

Rocap Number(s):
Heat Number(s): 10648850
Nut Mfg. Lot Number(s): S01210302H
Washer Mfg. Lot Number(s):
Bolt Specification: None
Bolt Length(s):
Nut Specification: A563 Coupling Nut
Washer Specification: None
Finish: F2329
Diameter/Size:
Bolt Mfg. Lot Number: 2103153-20
Rocap Test Requirement(s):
Lubricant Requirements(s):

Test Results

Test 1 of 1

DIME Test ID: 2021-10-20-21-1
Test Method: ASTM F606-14: Standard Test Methods for Determining the Mechanical Properties of Externally and Internally Threaded Fasteners, Washers, Direct Tension Indicators, and Rivets (Hex Cap Screws)
Verified Date: 10/26/2021
Date Tested: 10/22/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Nut Broke in Half
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 1
SampleSizeArea (in^2)Peak Load (lbf)Peak Load (kN)Tensile Strength (psi)Stress at Offset (psi)Load at Offset (lbf)Comments
1UNC 7/8 0.4626298328013624712284556755Nut Broke in Half
UTM 400kip
Temperature 72