Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 215161 DEA: 010C5704 EFIS: 0113000009
QA Service Level: 1
DIST-CO-RTE-PM: 01-HUM-101-69.8/75.2
Work Description: PLACE RHMA-G, HMA AND CONCRETE BARRIER.
Location Description: HUMBOLDT COUNTY IN AND NEAR EUREKA FROM 0.8 MILE SOUTH OF TOMPKINS HILL ROAD OVERHEAD TO 0.4 MILE NORTH OF HERRICK AVENUE OVERCROSSING
Contractor Name: MERCER-FRASER COMPANY
Contractor Address: 77 2nd St, Eureka, CA 95501
Resident Engineer: Joaquin Rodriguez Structure Rep.: Jarred Burrows
DIME Sample ID: 2021-09-08-7
TL Number from the TL Form: c972624
Sample Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Sample Organization Contact: (916) 227-7302
Type of Sample: Acceptance
Type of Material: Asphalt Binder
Sample Taken Date: 09/08/2021
Date that the sample was received by the laboratory/organization performing the testing: 09/13/2021
The quantity of what the sample constitutes: 1 can
A brief description of the sample: PG64-16
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Mercer Fraser Plant B
Performance Grade: PG 64-16
Modified: No
Lot number: 1
Sublot number: 1
Tank number:
Time of sample:
HMA Supplier:
Asphalt Binder Supplier: Valero Marketing & Supply - Benicia CA
Multigrade: No
Multigrade Type:
Asphalt Binder Mix Number:
DIME Test ID: 2021-09-08-7-1
Test Method: AASHTO T240-17: Standard Method of Test for Effect of Heat and Air on a Moving Film of Asphalt Binder (Rolling Thin-Film Oven Test)
Verified Date: 09/24/2021
Date Tested: 09/15/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: as per 2018 standard specs
Test Result Compliance: complies
Additional Comments When Verified:
Is mass change based on one or two containers?
|
Two
|
Any material loss from containers during heating process/testing?
|
No
|
Mass of empty container #1
|
174.393 grams
|
Mass of empty container #2
|
172.625 grams
|
Mass of container #1 before test (m1i)
|
209.870 grams
|
Mass of container #2 before test (m2i)
|
209.053 grams
|
Mass of container #1 after test (m1f)
|
209.711 grams
|
Mass of container #2 after test (m2f)
|
209.902 grams
|
Average mass change
|
0.941 percent
|
DIME Test ID: 2021-09-08-7-2
Test Method: AASHTO T315-20: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 09/24/2021
Date Tested: 09/14/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications ORG
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
Original binder
|
Test Plate Diameter
|
25 mm
|
Test Gap
|
1 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
12.00 %
|
Stress Amplitude
|
0.204 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
84.7 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
1.697 kPa
|
Test Temperature (Specimen 1)
|
64.0 C
|
Dynamic Shear, G*/sin(δ)
|
1.70 kPa
|
DIME Test ID: 2021-09-08-7-3
Test Method: AASHTO T315-20: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 09/24/2021
Date Tested: 09/14/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications RTFO
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
RTFO residue
|
Test Plate Diameter
|
25 mm
|
Test Gap
|
1 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
10.00 %
|
Stress Amplitude
|
0.566 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
77.8 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
5.660 kPa
|
Test Temperature (Specimen 1)
|
64.0 C
|
Dynamic Shear, G*/sin(δ)
|
5.79 kPa
|
DIME Test ID: 2021-09-08-7-4
Test Method: AASHTO T315-20: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 09/24/2021
Date Tested: 09/22/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications PAV
Test Result Compliance: complies
Additional Comments When Verified: pass
Phase
|
PAV residue
|
Test Plate Diameter
|
8 mm
|
Test Gap
|
2 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
1.00 %
|
Stress Amplitude
|
31.427 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
48.1 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
3142.342 kPa
|
Test Temperature (Specimen 1)
|
25.0 C
|
(G*) x sin(δ)=
|
2339 kPa
|
DIME Test ID: 2021-09-08-7-5
Test Method: AASHTO T313-19: Standard Method of Test for Determining the Flexural Creep Stiffness of Asphalt Binder Using the Bending Beam Rheometer (BBR)
Verified Date: 09/24/2021
Date Tested: 09/22/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: BBR per 2018 standard specifications
Test Result Compliance: complies
Additional Comments When Verified:
Minimum test bath temperature at 240 s
|
-6.0 C
|
Maximum test bath temperature at 240 s
|
-6.0 C
|
Time of test load application
|
no data HH:MM:SS
|
File name of test data
|
no data
|
Time beam in bath
|
no data
|
Time test started
|
no data HH:MM:SS
|
Flags issued by software during test
|
no data
|
Correlation coefficient (R²)
|
0
|
Regression coefficient a
|
no data
|
Regression coefficient b
|
no data
|
Regression coefficient c
|
no data
|
Load at time 0.0
|
0.0 mN
|
Deflection at time 0.0 s
|
0.000 µm
|
Load at time 0.5 s
|
0.0 mN
|
Deflection at time 0.5 s
|
0.000 µm
|
Load at 60.0 s
|
974.0 mN
|
Beam deflection 60.0 s
|
1.204 µm
|
Measured Stiffness Modulus 60.0 s
|
65.200 mPa
|
Estimated Stiffness Modulus 60.0 s
|
65.000 mPa
|
Difference between stiffness moduli 60.0 s
|
no data
|
Estimated m-value 60.0 s
|
0.399
|