Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 7780 DEA: 112T1824 EFIS: 1100020051
QA Service Level: 1
DIST-CO-RTE-PM: 11-SD-805-4.7/5.6
Work Description: REPLACE STRUCTURE AND CONSTRUCT DIRECT ACCESS RAMP (DAR).
Location Description: SAN DIEGO COUNTY IN CHULA VISTA FROM 0.4 MILE SOUTH OF EAST PALOMAR STREET OVERCROSSING TO 0.1 MILE NORTH OF NAPLES STREET UNDERCROSSING
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: 5860 El Camino Real #200, Carlsbad, CA 92008
Resident Engineer: Tom Davis Structure Rep.: Anh Ma
DIME Sample ID: 2014-08-14-7
TL Number from the TL Form:
Sample Submitted By Organization: Leighton Consulting, Incorporated - San Diego
Sample Organization Contact: (858) 292-8030
Type of Sample: Verification
Type of Material: Concrete
Sample Taken Date: 08/14/2014
Date that the sample was received by the laboratory/organization performing the testing: 08/15/2014
The quantity of what the sample constitutes: 13 cylinders
A brief description of the sample: concrete cylinders
From where was the sample collected: Other
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: jobsite
The concrete mix design number: 104009F
The truck number from where the sample was collected: 125519
The batch plant ticket number from where the sample was collected: 125519
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Palomar Bridge Deck middle portion
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2014-08-14-7-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 08/26/2014
Date Tested: 08/17/2014
Submitted By Organization: Leighton Consulting, Incorporated - San Diego
Organization Address: 3934 Murphy Canyon Road, B205,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92123
Organization Email: scolorado@leightongroup.com
Organization Phone: 8583008490
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength of cylinder (to nearest 10 psi)
|
2660 psi
|
Average diameter of cylinder 1
|
6.02 in
|
Maximum load on cylinder 1
|
75590 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Age of specimen
|
3 days
|
DIME Test ID: 2014-08-14-7-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 08/26/2014
Date Tested: 08/19/2014
Submitted By Organization: Leighton Consulting, Incorporated - San Diego
Organization Address: 3934 Murphy Canyon Road, B205,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92123
Organization Email: scolorado@leightongroup.com
Organization Phone: 8583008490
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength of cylinder (to nearest 10 psi)
|
2700 psi
|
Average diameter of cylinder 1
|
6.01 in
|
Maximum load on cylinder 1
|
76520 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Age of specimen
|
5 days
|
DIME Test ID: 2014-08-14-7-3
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 08/26/2014
Date Tested: 08/21/2014
Submitted By Organization: Leighton Consulting, Incorporated - San Diego
Organization Address: 3934 Murphy Canyon Road, B205,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92123
Organization Email: scolorado@leightongroup.com
Organization Phone: 8583008490
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.46 in^2
|
Cross sectional area of cylinder 2
|
28.46 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
3040 psi
|
Average diameter of cylinder 1
|
6.02 in
|
Average diameter of cylinder 2
|
6.02 in
|
Compressive strength of cylinder 1
|
3157.1 psi
|
Compressive strength of cylinder 2
|
2919.5 psi
|
Maximum load on cylinder 1
|
89850 lb
|
Maximum load on cylinder 2
|
83090 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
7 days
|
DIME Test ID: 2014-08-14-7-4
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 08/26/2014
Date Tested: 08/22/2014
Submitted By Organization: Leighton Consulting, Incorporated - San Diego
Organization Address: 3934 Murphy Canyon Road, B205,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92123
Organization Email: scolorado@leightongroup.com
Organization Phone: 8583008490
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.46 in^2
|
Cross sectional area of cylinder 2
|
28.46 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
3060 psi
|
Average diameter of cylinder 1
|
6.02 in
|
Average diameter of cylinder 2
|
6.02 in
|
Compressive strength of cylinder 1
|
3104.7 psi
|
Compressive strength of cylinder 2
|
3018.6 psi
|
Maximum load on cylinder 1
|
88360 lb
|
Maximum load on cylinder 2
|
85910 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
8 days
|
DIME Test ID: 2014-08-14-7-5
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 08/26/2014
Date Tested: 08/24/2014
Submitted By Organization: Leighton Consulting, Incorporated - San Diego
Organization Address: 3934 Murphy Canyon Road, B205,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92123
Organization Email: scolorado@leightongroup.com
Organization Phone: 8583008490
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.46 in^2
|
Cross sectional area of cylinder 2
|
28.46 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
3320 psi
|
Average diameter of cylinder 1
|
6.02 in
|
Average diameter of cylinder 2
|
6.02 in
|
Compressive strength of cylinder 1
|
3319.7 psi
|
Compressive strength of cylinder 2
|
3312.0 psi
|
Maximum load on cylinder 1
|
94480 lb
|
Maximum load on cylinder 2
|
94260 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
10 days
|
DIME Test ID: 2014-08-14-7-6
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 08/26/2014
Date Tested: 08/26/2014
Submitted By Organization: Leighton Consulting, Incorporated - San Diego
Organization Address: 3934 Murphy Canyon Road, B205,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92123
Organization Email: scolorado@leightongroup.com
Organization Phone: 8583008490
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength of cylinder (to nearest 10 psi)
|
3580 psi
|
Average diameter of cylinder 1
|
6.01 in
|
Maximum load on cylinder 1
|
101610 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Age of specimen
|
12 days
|
DIME Test ID: 2014-08-14-7-7
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 08/29/2014
Date Tested: 08/28/2014
Submitted By Organization: Leighton Consulting, Incorporated - San Diego
Organization Address: 3934 Murphy Canyon Road, B205,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92123
Organization Email: scolorado@leightongroup.com
Organization Phone: 8583008490
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength of cylinder (to nearest 10 psi)
|
3540 psi
|
Average diameter of cylinder 1
|
6.01 in
|
Maximum load on cylinder 1
|
100390 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Age of specimen
|
14 days
|
DIME Test ID: 2014-08-14-7-8
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Submitted By Organization: Leighton Consulting, Incorporated - San Diego
Organization Address: 3934 Murphy Canyon Road, B205,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92123
Organization Email: scolorado@leightongroup.com
Organization Phone: 8583008490
Data has not been verified.