Project ID: 215627 DEA: 032G2004 EFIS: 0321000024
QA Service Level: 1
DIST-CO-RTE-PM: 03-YOL-128-0.0/9.8
Work Description: PLACE RHMA AND REPLACE ASPHALT CONCRETE.
Location Description: YOLO COUNTY IN AND NEAR WINTERS FROM PUTAH CREEK BRIDGE TO ROUTE 128/505 SEPARATION
Contractor Name: LAMON CONSTRUCTION
Contractor Address: 871 Von Geldern Way, Yuba City, California 95991
Resident Engineer: David Maher Structure Rep.: Unknown
DIME Sample ID: 2021-08-11-26
TL Number from the TL Form: 042879
Sample Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Sample Organization Contact: (916) 227-7302
Type of Sample: Acceptance
Type of Material: Asphalt Binder
Sample Taken Date: 08/11/2021
Date that the sample was received by the laboratory/organization performing the testing: 08/27/2021
The quantity of what the sample constitutes: 3 cans
A brief description of the sample: TEST 8/11, NO TEST 8/18
From where was the sample collected: Source
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Marathon
Performance Grade: PG 64-16
Modified:
Lot number: 1
Sublot number: 1
Tank number:
Time of sample:
HMA Supplier:
Asphalt Binder Supplier: Marathon Petroleum Co. LP - Elk Grove CA
Multigrade: No
Multigrade Type:
Asphalt Binder Mix Number:
DIME Test ID: 2021-08-11-26-1
Test Method: AASHTO T240-17: Standard Method of Test for Effect of Heat and Air on a Moving Film of Asphalt Binder (Rolling Thin-Film Oven Test)
Verified Date: 09/13/2021
Date Tested: 09/01/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: as per 2018 standard specs
Test Result Compliance: complies
Additional Comments When Verified:
Is mass change based on one or two containers?
|
Two
|
Any material loss from containers during heating process/testing?
|
No
|
Mass of empty container #1
|
175.269 grams
|
Mass of empty container #2
|
170.397 grams
|
Mass of container #1 before test (m1i)
|
210.838 grams
|
Mass of container #2 before test (m2i)
|
206.181 grams
|
Mass of container #1 after test (m1f)
|
210.639 grams
|
Mass of container #2 after test (m2f)
|
205.976 grams
|
Average mass change
|
-0.566 percent
|
DIME Test ID: 2021-08-11-26-2
Test Method: AASHTO T315-20: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 09/13/2021
Date Tested: 09/01/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications OG
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
Original binder
|
Test Plate Diameter
|
25 mm
|
Test Gap
|
1 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
12.00 %
|
Stress Amplitude
|
0.167 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
87.6 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
1.393 kPa
|
Test Temperature (Specimen 1)
|
64.0 C
|
Dynamic Shear, G*/sin(δ)
|
1.39 kPa
|
DIME Test ID: 2021-08-11-26-3
Test Method: AASHTO T315-20: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 09/13/2021
Date Tested: 09/01/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications RTFO
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
RTFO residue
|
Test Plate Diameter
|
25 mm
|
Test Gap
|
1 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
10.00 %
|
Stress Amplitude
|
0.400 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
84.2 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
3.996 kPa
|
Test Temperature (Specimen 1)
|
64.0 C
|
Dynamic Shear, G*/sin(δ)
|
4.02 kPa
|
DIME Test ID: 2021-08-11-26-4
Test Method: AASHTO T315-20: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 09/13/2021
Date Tested: 09/08/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications PAV
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
PAV residue
|
Test Plate Diameter
|
8 mm
|
Test Gap
|
2 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
1.00 %
|
Stress Amplitude
|
49.656 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
50.7 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
4964.940 kPa
|
Test Temperature (Specimen 1)
|
28.0 C
|
(G*) x sin(δ)=
|
3842 kPa
|
DIME Test ID: 2021-08-11-26-5
Test Method: AASHTO T313-19: Standard Method of Test for Determining the Flexural Creep Stiffness of Asphalt Binder Using the Bending Beam Rheometer (BBR)
Verified Date: 09/13/2021
Date Tested: 09/08/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications
Test Result Compliance: complies
Additional Comments When Verified:
Minimum test bath temperature at 240 s
|
-6.1 C
|
Maximum test bath temperature at 240 s
|
-6.0 C
|
Time of test load application
|
no data HH:MM:SS
|
File name of test data
|
no data
|
Time beam in bath
|
no data
|
Time test started
|
no data HH:MM:SS
|
Flags issued by software during test
|
no data
|
Correlation coefficient (R²)
|
0
|
Regression coefficient a
|
no data
|
Regression coefficient b
|
no data
|
Regression coefficient c
|
no data
|
Load at time 0.0
|
0.0 mN
|
Deflection at time 0.0 s
|
0.000 µm
|
Load at time 0.5 s
|
0.0 mN
|
Deflection at time 0.5 s
|
0.000 µm
|
Load at 60.0 s
|
0.0 mN
|
Beam deflection 60.0 s
|
0.000 µm
|
Measured Stiffness Modulus 60.0 s
|
87.500 mPa
|
Estimated Stiffness Modulus 60.0 s
|
87.400 mPa
|
Difference between stiffness moduli 60.0 s
|
no data
|
Estimated m-value 60.0 s
|
0.406
|