Print Report | Back to Sample Detail

Sample Record for 2021-07-15-40

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 214114 DEA: 040A5394 EFIS: 0418000244 QA Service Level: 1
DIST-CO-RTE-PM: 04-SOL-80,12-11.4/12.8, 2.1/2.8
Work Description: Widen EB SR-12 Connector, Construct 3 ramps & 2 box girder bridges, remove existing bridge, etc.
Location Description: I-80/I-680/Route 12 Interchange
Contractor Name: Kiewit Infrastructure West Co.
Contractor Address: 4650 Business Center Drive, Fairfield, CA 94534
Resident Engineer: Cassaundra Lograsso Structure Rep.: Kambiz Kouchesfahani

Sample Information

DIME Sample ID: 2021-07-15-40
TL Number from the TL Form:
Sample Submitted By Organization: Construction Testing Services
Sample Organization Contact: (925) 351-6905
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 07/15/2021
Date that the sample was received by the laboratory/organization performing the testing: 07/16/2021
The quantity of what the sample constitutes: 414 Cy
A brief description of the sample: 6x12 concrete cylinders (set 1 of 5)
From where was the sample collected: Job Site
Laboratory sample identification: 233060
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Cemex Cordelia

Material Information

The concrete mix design number: 1619340
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 29744608
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Back of Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 1

DIME Test ID: 2021-07-15-40-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 08/23/2021
Date Tested: 08/12/2021
Submitted By Organization: Construction Testing Services
Organization Address: 2118 Rheem Drive,
Organization City: Pleasanton
Organization State: CA
Organization Zipcode: 94588
Organization Email: rring@cts-1.com
Organization Phone: (925) 351-6905
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 1
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength of cylinder (to nearest 10 psi) 7360 psi
Average diameter of cylinder 1 6.00 in
Maximum load on cylinder 1 207900 lb
Type of fracture pattern of cylinder 1 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Age of specimen 28 days