Sample Record for 2021-07-20-10
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 215188 DEA: 080F5434 EFIS: 0817000239 Permit Numbers: 0823NMC0369
QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-I-15,SR-91-6.1-7.6
Work Description: I-15 ELC: 15/91 Express Lanes Connector Project (ELC)
Location Description: Junction of I-15 and SR-91 in Corona, CA
Contractor Name: Myers-Rados Joint Venture
Contractor Address: 629 N. Main Street, Suite C3, Corona, CA 92878
Resident Engineer: Roy Fisher Structure Rep.: Alhakem Alina
Sample Information
DIME Sample ID: 2021-07-20-10
TL Number from the TL Form: 1026-720
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 07/20/2021
Date that the sample was received by the laboratory/organization performing the testing: 07/21/2021
The quantity of what the sample constitutes: 8 CYLINDERS
A brief description of the sample: CONCRETE CYLINDERS
From where was the sample collected: Job Site
Laboratory sample identification: 1026-720
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: NA
Material Information
The concrete mix design number: 1610974
The truck number from where the sample was collected: NA
The batch plant ticket number from where the sample was collected: NA
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: NA
Where the material sample would have been placed if not sampled: NA
From Lot No.:
Bag Lot No.:
Test Results
Test 1 of 4
DIME Test ID: 2021-07-20-10-1
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 07/27/2021
Date Tested: 07/27/2021
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Average diameter of cylinder 1
|
5.99 in
|
Average diameter of cylinder 2
|
5.99 in
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Cross sectional area of cylinder 1
|
28.18 in^2
|
Cross sectional area of cylinder 2
|
28.18 in^2
|
Compressive strength (to nearest 10 psi)
|
3320 psi
|
Maximum load on cylinder 1
|
95000 lb
|
Maximum load on cylinder 2
|
91850 lb
|
Compressive strength of cylinder 1
|
3371.2 psi
|
Type of fracture pattern of cylinder 1
|
2
|
Compressive strength of cylinder 2
|
3259.4 psi
|
Type of fracture pattern of cylinder 2
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
7 days
|
Age of specimen in hours
|
0 hours
|
Test 2 of 4
DIME Test ID: 2021-07-20-10-2
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 08/03/2021
Date Tested: 08/03/2021
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Average diameter of cylinder 1
|
5.99 in
|
Average diameter of cylinder 2
|
5.99 in
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Cross sectional area of cylinder 1
|
28.18 in^2
|
Cross sectional area of cylinder 2
|
28.18 in^2
|
Compressive strength (to nearest 10 psi)
|
4120 psi
|
Maximum load on cylinder 1
|
115565 lb
|
Maximum load on cylinder 2
|
116832 lb
|
Compressive strength of cylinder 1
|
4101.0 psi
|
Type of fracture pattern of cylinder 1
|
2
|
Compressive strength of cylinder 2
|
4145.9 psi
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
14 days
|
Age of specimen in hours
|
0 hours
|
Test 3 of 4
DIME Test ID: 2021-07-20-10-3
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 08/10/2021
Date Tested: 08/10/2021
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Average diameter of cylinder 1
|
5.99 in
|
Average diameter of cylinder 2
|
5.99 in
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Cross sectional area of cylinder 1
|
28.18 in^2
|
Cross sectional area of cylinder 2
|
28.18 in^2
|
Compressive strength (to nearest 10 psi)
|
4640 psi
|
Maximum load on cylinder 1
|
131760 lb
|
Maximum load on cylinder 2
|
129840 lb
|
Compressive strength of cylinder 1
|
4675.7 psi
|
Type of fracture pattern of cylinder 1
|
2
|
Compressive strength of cylinder 2
|
4607.5 psi
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
21 days
|
Age of specimen in hours
|
0 hours
|
Test 4 of 4
DIME Test ID: 2021-07-20-10-4
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 08/17/2021
Date Tested: 08/17/2021
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Average diameter of cylinder 1
|
6.01 in
|
Average diameter of cylinder 2
|
6.00 in
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Cross sectional area of cylinder 1
|
28.37 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Compressive strength (to nearest 10 psi)
|
4660 psi
|
Maximum load on cylinder 1
|
132090 lb
|
Maximum load on cylinder 2
|
131820 lb
|
Compressive strength of cylinder 1
|
4656.0 psi
|
Type of fracture pattern of cylinder 1
|
2
|
Compressive strength of cylinder 2
|
4662.9 psi
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
0 hours
|