Print Report | Back to Sample Detail

Sample Record for 2021-07-16-31

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 215350 DEA: 081E0604 EFIS: 0813000140 QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-18-97.0/99.5
Work Description: WIDEN ROADWAY WITH HMA, MINOR CONCRETE & MODIFY SIGNAL & LIGHTING.
Location Description: SAN BERNARDINO COUNTY IN VICTORVILLE FROM AMARGOSA ROAD TO COBALT ROAD
Contractor Name: SULLY-MILLER CONTRACTING COMPANY
Contractor Address: 135 S STATE COLLEGE BLVD #400, BREA CA 92821
Resident Engineer: Larry Canuti Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2021-07-16-31
TL Number from the TL Form: 146305
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 07/16/2021
Date that the sample was received by the laboratory/organization performing the testing: 07/19/2021
The quantity of what the sample constitutes: 6
A brief description of the sample: 6x12
From where was the sample collected: Job Site
Laboratory sample identification: 1031-05
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: np

Material Information

The concrete mix design number: np
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: np
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: np
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 2

DIME Test ID: 2021-07-16-31-1
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 07/23/2021
Date Tested: 07/23/2021
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Average diameter of cylinder 1 6.01 in
Average diameter of cylinder 2 6.01 in
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Cross sectional area of cylinder 1 28.37 in^2
Cross sectional area of cylinder 2 28.37 in^2
Compressive strength (to nearest 10 psi) 3490 psi
Maximum load on cylinder 1 99715 lb
Maximum load on cylinder 2 98240 lb
Compressive strength of cylinder 1 3514.8 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 3462.8 psi
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 7 days
Age of specimen in hours 0 hours

Test 2 of 2

DIME Test ID: 2021-07-16-31-2
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 08/13/2021
Date Tested: 08/13/2021
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Average diameter of cylinder 1 6.01 in
Average diameter of cylinder 2 6.02 in
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Cross sectional area of cylinder 1 28.37 in^2
Cross sectional area of cylinder 2 28.46 in^2
Compressive strength (to nearest 10 psi) 4550 psi
Maximum load on cylinder 1 128315 lb
Maximum load on cylinder 2 130405 lb
Compressive strength of cylinder 1 4522.9 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 4582.0 psi
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 28 days
Age of specimen in hours 0 hours