Project ID: 213762 DEA: 032F3404 EFIS: 0300020616
QA Service Level: 1
DIST-CO-RTE-PM: 03-PLA-49-3.1/7.5
Work Description: WIDEN SHOULDERS, ADD RETAINING WALLS, REPLACE MBGR, CURBS & ELECTRICAL
Location Description: PLACER COUNTY IN AND NEAR AUBURN FROM 0.1 MILE SOUTH OF ROUTE 49/80 SEPARATION TO 0.1 MILE NORTH OF DRY CREEK ROAD
Contractor Name: FLATIRON WEST INC
Contractor Address: 2100 GOODYEAR ROAD, BENICIA, CA 94510
Resident Engineer: Jeff Johnson Structure Rep.: Unknown
DIME Sample ID: 2021-06-28-30
TL Number from the TL Form: c930959
Sample Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Sample Organization Contact: (916) 227-7302
Type of Sample: Department Acceptance
Type of Material: Asphalt Binder
Sample Taken Date: 06/28/2021
Date that the sample was received by the laboratory/organization performing the testing: 07/02/2021
The quantity of what the sample constitutes: 1 of 1 can
A brief description of the sample: PG64-16
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: KFC - Hallwood
Performance Grade: PG 64-16
Modified: No
Lot number:
Sublot number:
Tank number:
Time of sample:
HMA Supplier:
Certified Asphalt Supplier: Marathon Petroleum Co. LP - Elk Grove CA
Multigrade: No
Multigrade Type:
Asphalt Binder Mix Number:
DIME Test ID: 2021-06-28-30-1
Test Method: AASHTO T240-17: Standard Method of Test for Effect of Heat and Air on a Moving Film of Asphalt Binder (Rolling Thin-Film Oven Test)
Verified Date: 07/13/2021
Date Tested: 07/08/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications
Test Result Compliance: complies
Additional Comments When Verified:
Is mass change based on one or two containers?
|
Two
|
Any material loss from containers during heating process/testing?
|
No
|
Mass of empty container #1
|
160.664 grams
|
Mass of empty container #2
|
161.683 grams
|
Mass of container #1 before test (m1i)
|
195.828 grams
|
Mass of container #2 before test (m2i)
|
197.001 grams
|
Mass of container #1 after test (m1f)
|
195.694 grams
|
Mass of container #2 after test (m2f)
|
196.868 grams
|
Average mass change
|
-0.379 percent
|
DIME Test ID: 2021-06-28-30-2
Test Method: AASHTO T315-20: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 07/13/2021
Date Tested: 07/08/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications ORG
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
Original binder
|
Test Plate Diameter
|
25 mm
|
Test Gap
|
1 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
12.00 %
|
Stress Amplitude
|
0.181 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
85.7 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
1.506 kPa
|
Test Temperature (Specimen 1)
|
64.0 C
|
Dynamic Shear, G*/sin(δ)
|
1.51 kPa
|
DIME Test ID: 2021-06-28-30-3
Test Method: AASHTO T315-20: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 07/13/2021
Date Tested: 07/08/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications RTFO
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
RTFO residue
|
Test Plate Diameter
|
25 mm
|
Test Gap
|
1 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
10.00 %
|
Stress Amplitude
|
0.428 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
80.6 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
4.284 kPa
|
Test Temperature (Specimen 1)
|
64.0 C
|
Dynamic Shear, G*/sin(δ)
|
4.34 kPa
|
DIME Test ID: 2021-06-28-30-4
Test Method: AASHTO T315-20: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 07/13/2021
Date Tested: 07/12/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications PAV
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
PAV residue
|
Test Plate Diameter
|
8 mm
|
Test Gap
|
2 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
1.00 %
|
Stress Amplitude
|
53.523 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
45.0 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
5352.366 kPa
|
Test Temperature (Specimen 1)
|
28.0 C
|
(G*) x sin(δ)=
|
3785 kPa
|
DIME Test ID: 2021-06-28-30-5
Test Method: AASHTO T313-19: Standard Method of Test for Determining the Flexural Creep Stiffness of Asphalt Binder Using the Bending Beam Rheometer (BBR)
Verified Date: 07/13/2021
Date Tested: 07/12/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications
Test Result Compliance: complies
Additional Comments When Verified:
Minimum test bath temperature at 240 s
|
-6.0 C
|
Maximum test bath temperature at 240 s
|
-6.0 C
|
Time of test load application
|
no data HH:MM:SS
|
File name of test data
|
no data
|
Time beam in bath
|
no data
|
Time test started
|
no data HH:MM:SS
|
Flags issued by software during test
|
no data
|
Correlation coefficient (R²)
|
0
|
Regression coefficient a
|
no data
|
Regression coefficient b
|
no data
|
Regression coefficient c
|
no data
|
Load at time 0.0
|
0.0 mN
|
Deflection at time 0.0 s
|
0.000 µm
|
Load at time 0.5 s
|
0.0 mN
|
Deflection at time 0.5 s
|
0.000 µm
|
Load at 60.0 s
|
981.0 mN
|
Beam deflection 60.0 s
|
0.827 µm
|
Measured Stiffness Modulus 60.0 s
|
95.600 mPa
|
Estimated Stiffness Modulus 60.0 s
|
95.600 mPa
|
Difference between stiffness moduli 60.0 s
|
no data
|
Estimated m-value 60.0 s
|
0.362
|