Project ID: 214899 DEA: 033H4504 EFIS: 0318000001
QA Service Level: 1
DIST-CO-RTE-PM: 03-ED-50-33.8/34.2
Work Description: CONSTRUCT RW, WIDEN RDWY, COLD PLANE AC PVMT, & HMA OVERLAY.
Location Description: EL DORADO COUNTY AT FRESH POND FROM 0.6 TO 0.2 MILE WEST OF FOREST ROAD/OUTER LIMITS LANE
Contractor Name: BRIDGEWAY CIVIL CONSTRUCTORS, INC.
Contractor Address: 4950 Allison Parkway, # A, Vacaville, CA 95866
Resident Engineer: Jody Phillips Structure Rep.: Dave Carlin
DIME Sample ID: 2021-06-02-2
TL Number from the TL Form: 79401
Sample Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Sample Organization Contact: (916) 594-1991
Type of Sample: Quality Assurance
Type of Material: Cementitious
Sample Taken Date: 06/02/2021
Date that the sample was received by the laboratory/organization performing the testing: 06/03/2021
The quantity of what the sample constitutes: 12 Cubes
A brief description of the sample: Grout Cubes
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name: Soldier Pile Wall
The fabricator/manufacturer/facility name: Pacific Coast Drilling Company
DIME Test ID: 2021-06-02-2-1
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 06/05/2021
Date Tested: 06/04/2021
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test: 2 Day
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no
|
Age of specimen
|
2 days
|
The amount of flow
|
no data %
|
The amount of water used
|
48.5 %
|
Compressive strength of 1st specimen
|
3030 psi
|
Compressive strength of 2nd specimen
|
2839 psi
|
Compressive strength of 3rd specimen
|
2910 psi
|
Average Compressive strength (to nearest 10 psi)
|
2930 psi
|
DIME Test ID: 2021-06-02-2-2
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 06/05/2021
Date Tested: 06/05/2021
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test: Specimen 3 was eliminated from the average for being outside allowable limits per Section 12 of ASTM C109
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no
|
Age of specimen
|
3 days
|
The amount of flow
|
no data %
|
The amount of water used
|
48.5 %
|
Compressive strength of 1st specimen
|
3743 psi
|
Compressive strength of 2nd specimen
|
3737 psi
|
Compressive strength of 3rd specimen
|
3936 psi
|
Average Compressive strength (to nearest 10 psi)
|
3810 psi
|
DIME Test ID: 2021-06-02-2-3
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 06/06/2021
Date Tested: 06/06/2021
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test: Specimen 2 was eliminated from the average for being outside allowable limits per Section 12 of ASTM C109
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no
|
Age of specimen
|
4 days
|
The amount of flow
|
no data %
|
The amount of water used
|
48.5 %
|
Compressive strength of 1st specimen
|
4495 psi
|
Compressive strength of 2nd specimen
|
4052 psi
|
Compressive strength of 3rd specimen
|
4424 psi
|
Average Compressive strength (to nearest 10 psi)
|
4460 psi
|
DIME Test ID: 2021-06-02-2-4
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 06/09/2021
Date Tested: 06/09/2021
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test: 7 Day; Specimen 2 excluded for being out of range of other two specimens per ASTM C109-20.
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no
|
Age of specimen
|
7 days
|
The amount of flow
|
no data %
|
The amount of water used
|
48.5 %
|
Compressive strength of 1st specimen
|
5180 psi
|
Compressive strength of 2nd specimen
|
4990 psi
|
Compressive strength of 3rd specimen
|
5161 psi
|
Average Compressive strength (to nearest 10 psi)
|
5110 psi
|