Project ID: 214700 DEA: 030F2804 EFIS: 0312000069
QA Service Level: 1
DIST-CO-RTE-PM: 03-SAC-99-7.1/9.4
Work Description: Dillard Overcrossing and McConnel Overhead
Location Description: Hwy 99, Elk Grove, CA
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: 4001 Bradshaw Road, Sacramento, CA 95827
Resident Engineer: Saed Masoud Structure Rep.: Chau Ha
DIME Sample ID: 2021-05-18-11
TL Number from the TL Form: 850183
Sample Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Sample Organization Contact: (916) 227-7302
Type of Sample: Acceptance
Type of Material: Asphalt Binder
Sample Taken Date: 05/18/2021
Date that the sample was received by the laboratory/organization performing the testing: 05/20/2021
The quantity of what the sample constitutes: 1 of 1
A brief description of the sample: PG64-16
From where was the sample collected: Source
Laboratory sample identification: 1628199965
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Valero
Performance Grade: PG 64-16
Modified: No
Lot number: 4
Sublot number: 15
Tank number:
Time of sample:
HMA Supplier:
Certified Asphalt Supplier: Valero Marketing & Supply - Benicia CA
Multigrade: No
Multigrade Type:
Asphalt Binder Mix Number:
DIME Test ID: 2021-05-18-11-1
Test Method: AASHTO T240-17: Standard Method of Test for Effect of Heat and Air on a Moving Film of Asphalt Binder (Rolling Thin-Film Oven Test)
Verified Date: 06/01/2021
Date Tested: 05/26/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: per 2018 standard specs
Test Result Compliance: complies
Additional Comments When Verified:
Is mass change based on one or two containers?
|
Two
|
Any material loss from containers during heating process/testing?
|
No
|
Mass of empty container #1
|
176.436 grams
|
Mass of empty container #2
|
177.662 grams
|
Mass of container #1 before test (m1i)
|
211.722 grams
|
Mass of container #2 before test (m2i)
|
213.068 grams
|
Mass of container #1 after test (m1f)
|
211.591 grams
|
Mass of container #2 after test (m2f)
|
212.947 grams
|
Average mass change
|
-0.357 percent
|
DIME Test ID: 2021-05-18-11-3
Test Method: AASHTO T315-16: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 06/01/2021
Date Tested: 05/26/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications ORIG
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
Original binder
|
Test Plate Diameter
|
25 mm
|
Test Gap
|
1 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
12.00 %
|
Stress Amplitude
|
0.175 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
85.4 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
1.455 kPa
|
Test Temperature (Specimen 1)
|
64.0 C
|
Dynamic Shear, G*/sin(δ)
|
1.46 kPa
|
DIME Test ID: 2021-05-18-11-4
Test Method: AASHTO T315-16: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 06/01/2021
Date Tested: 05/26/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 standard specs RTFO
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
RTFO residue
|
Test Plate Diameter
|
25 mm
|
Test Gap
|
1 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
10.00 %
|
Stress Amplitude
|
0.360 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
80.9 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
3.598 kPa
|
Test Temperature (Specimen 1)
|
64.0 C
|
Dynamic Shear, G*/sin(δ)
|
3.64 kPa
|
DIME Test ID: 2021-05-18-11-5
Test Method: AASHTO T315-16: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 06/01/2021
Date Tested: 05/28/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 standard specs PAV
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
PAV residue
|
Test Plate Diameter
|
8 mm
|
Test Gap
|
2 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
1.00 %
|
Stress Amplitude
|
29.839 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
48.5 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
2983.641 kPa
|
Test Temperature (Specimen 1)
|
28.0 C
|
(G*) x sin(δ)=
|
2235 kPa
|
DIME Test ID: 2021-05-18-11-6
Test Method: AASHTO T313-19: Standard Method of Test for Determining the Flexural Creep Stiffness of Asphalt Binder Using the Bending Beam Rheometer (BBR)
Verified Date: 06/01/2021
Date Tested: 06/01/2021
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standard Specifications
Test Result Compliance: complies
Additional Comments When Verified:
Minimum test bath temperature at 240 s
|
-6.0 C
|
Maximum test bath temperature at 240 s
|
-6.0 C
|
Time of test load application
|
no data HH:MM:SS
|
File name of test data
|
no data
|
Time beam in bath
|
no data
|
Time test started
|
no data HH:MM:SS
|
Flags issued by software during test
|
no data
|
Correlation coefficient (R²)
|
0
|
Regression coefficient a
|
no data
|
Regression coefficient b
|
no data
|
Regression coefficient c
|
no data
|
Load at time 0.0
|
0.0 mN
|
Deflection at time 0.0 s
|
0.000 µm
|
Load at time 0.5 s
|
0.0 mN
|
Deflection at time 0.5 s
|
0.000 µm
|
Load at 60.0 s
|
0.0 mN
|
Beam deflection 60.0 s
|
0.000 µm
|
Measured Stiffness Modulus 60.0 s
|
64.500 mPa
|
Estimated Stiffness Modulus 60.0 s
|
64.500 mPa
|
Difference between stiffness moduli 60.0 s
|
no data
|
Estimated m-value 60.0 s
|
0.413
|