Sample Record for 2021-05-13-8
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 214355 DEA: 120K0214 EFIS: 1214000096
QA Service Level: 1
DIST-CO-RTE-PM: 12-ORA-5-12.4/14.5
Work Description: South County Improvement Project (Phase 1 - Avery/Crown Valley) PLACE HMA, INSTALL CONC PAVEMENT, RETAIN WALL, MODIFY ELECT SYS. | Add one lane btwn 73 & Oso PKWY
Location Description: ORANGE COUNTY IN SAN JUAN CAPISTRANO, LAGUNA HILLS, LAGUNA NIGUEL AND MISSION VIEJO FROM 0.5 MILE SOUTH OF AVERY PARKWAY UNDERCROSSING TO 0.8 MILE NORTH OF CROWN VALLEY PARKWAY OVERCROSSING
Contractor Name: ORTIZ ENTERPRISES, INC.
Contractor Address: 6 Cushing, Suite 200, Irvine, CA 92618
Resident Engineer: Artin Merati Structure Rep.: Imad Karam
Sample Information
DIME Sample ID: 2021-05-13-8
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Headed Bars
Sample Taken Date: 05/13/2021
Date that the sample was received by the laboratory/organization performing the testing: 05/14/2021
The quantity of what the sample constitutes: (8) nVent LENTON TERMINATOR (D14) with LENTON PLUS cold worked taper threaded rebar
A brief description of the sample: nVent LENTON TERMINATOR (D14) with LENTON PLUS cold worked taper threaded rebar
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Coreslab Structures L A Inc
Material Information
Production or Authorization Testing: Production Testing
Rebar Heat Number(s): 4102817
Head Manufacturer Lot Number(s): L9805 L9766
Rebar Size: #8
Headed Bar Model Name: 9TT 17 02
Size of Head: Full Size - 9x
Head Connection Type: Taper Threaded
Head Shape: Circular
Rebar Manufacturer: CMC Steel Arizona
Head Manufacturer: ERICO International Corporation nVent
Head Fabricator: nVent Lenton
Material Standard Code: ASTM A706
Headed Bar Unique ID:
Test Results
Test 1 of 8
DIME Test ID: 2021-05-13-8-1
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 05/18/2021
Date Tested: 05/14/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Head Pull Off
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 1 | 0.79 | 78540 | 99418 | Head Pull Off | fsaylor |
| |
Temperature
|
72 f
|
UTM
|
400kip
|
Test 2 of 8
DIME Test ID: 2021-05-13-8-2
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 05/18/2021
Date Tested: 05/14/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Head Pull Off
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 1 | 0.79 | 80379 | 101746 | Head Pull Off | fsaylor |
| |
Temperature
|
72 f
|
UTM
|
400kip
|
Test 3 of 8
DIME Test ID: 2021-05-13-8-3
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 05/18/2021
Date Tested: 05/14/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Head Pull Off
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 1 | 0.79 | 80061 | 101343 | Head Pull Off | fsaylor |
| |
Temperature
|
72 f
|
UTM
|
400kip
|
Test 4 of 8
DIME Test ID: 2021-05-13-8-4
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 05/18/2021
Date Tested: 05/14/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Head Pull Off
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 1 | 0.79 | 77516 | 98121 | Head Pull Off | fsaylor |
| |
Temperature
|
72 f
|
UTM
|
400kip
|
Test 5 of 8
DIME Test ID: 2021-05-13-8-5
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 05/18/2021
Date Tested: 05/14/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Head Pull Off
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 2 | 0.79 | 79908 | 101149 | Head Pull Off | fsaylor |
| |
Temperature
|
72 f
|
UTM
|
400kip
|
Test 6 of 8
DIME Test ID: 2021-05-13-8-6
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 05/18/2021
Date Tested: 05/14/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Head Pull Off
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 2 | 0.79 | 79375 | 100475 | Head Pull Off | fsaylor |
| |
Temperature
|
72 f
|
UTM
|
400kip
|
Test 7 of 8
DIME Test ID: 2021-05-13-8-7
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 05/18/2021
Date Tested: 05/14/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Head Pull Off
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 2 | 0.79 | 77416 | 97995 | Head Pull Off | fsaylor |
| |
Temperature
|
72 f
|
UTM
|
400kip
|
Test 8 of 8
DIME Test ID: 2021-05-13-8-8
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 05/18/2021
Date Tested: 05/14/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Head Pull Off
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 2 | 0.79 | 79352 | 100446 | Head Pull Off | fsaylor |
| |
Temperature
|
72 f
|
UTM
|
400kip
|