DIME Sample ID: 2021-03-17-37
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Sample Organization Contact: (916) 227-7071
Type of Sample: Authorization
Type of Material: Cementitious
Sample Taken Date: 03/17/2021
Date that the sample was received by the laboratory/organization performing the testing: 03/17/2021
The quantity of what the sample constitutes: 1 Bucket
A brief description of the sample: Portland Cement
From where was the sample collected: Source
Laboratory sample identification: CM215189
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: CALPORTLAND

Material Information

Brand: CalPortland
Mill: Siam SCG
Type of Cementitious Material: Type II Cement

Test Results

Test 1 of 5

DIME Test ID: 2021-03-17-37-2
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 06/03/2021
Date Tested: 04/23/2021
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 3 DAY TEST
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Age of specimen 7 days
The amount of flow 110 %
The amount of water used 48.5 %
Compressive strength of 1st specimen 4154 psi
Compressive strength of 2nd specimen 4172 psi
Compressive strength of 3rd specimen 4094 psi
Average Compressive strength (to nearest 10 psi) 4140 psi

Test 2 of 5

DIME Test ID: 2021-03-17-37-3
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 06/03/2021
Date Tested: 04/27/2021
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 7 DAY TEST
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Age of specimen 7 days
The amount of flow 110 %
The amount of water used 48.5 %
Compressive strength of 1st specimen 4886 psi
Compressive strength of 2nd specimen 5193 psi
Compressive strength of 3rd specimen 5249 psi
Average Compressive strength (to nearest 10 psi) 5110 psi

Test 3 of 5

DIME Test ID: 2021-03-17-37-4
Test Method: ASTM C191-13: Standard Test Methods for Time of Setting of Hydraulic Cement by Vicat Needle
Verified Date: 06/03/2021
Date Tested: 05/05/2021
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Type of Water Used Type IV grade reagent water
Initial time of setting 148 min
Final time of setting no data

Test 4 of 5

DIME Test ID: 2021-03-17-37-5
Test Method: ASTM C185-15a: Standard Test Method for Air Content of Hydraulic Cement Mortar
Verified Date: 06/03/2021
Date Tested: 04/29/2021
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Specific gravity 3.15
Water Content 240
The amount of flow (In percent) 93 %
The amount of water used (In percent) 68.57 %
Net Weight of Sample 829.9 grams
Air Content 8 %

Test 5 of 5

DIME Test ID: 2021-03-17-37-6
Test Method: ASTM C204-11: Standard Test Methods for Fineness of Hydraulic Cement by Air-Permeability Apparatus
Verified Date: 06/03/2021
Date Tested: 04/20/2021
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Method Used Test Method A
Test Time 102 seconds
Fineness 4076 cm^2/g