Project Information

Project ID: 212112 DEA: 080C2514 EFIS: 0816000076 COOP: 081645 QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-10-0.0/13.2
Work Description: Design-Build of I-10 Corridor Contract 1 - Adding 2 new Express Lanes
Location Description: LA/SBD County Line to PM 13.2 near I-15
Contractor Name: Lane-Security Paving Joint Venture
Contractor Address: 3450 Centre Lake Drive, 1st Floor, Ontario, CA 91761
Resident Engineer: Jose Corona Structure Rep.: Luis Negrete

Sample Information

DIME Sample ID: 2021-04-02-8
TL Number from the TL Form: 1
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 04/02/2021
Date that the sample was received by the laboratory/organization performing the testing: 04/05/2021
The quantity of what the sample constitutes: 6
A brief description of the sample: 6x12
From where was the sample collected: Job Site
Laboratory sample identification: 1015-1A
Structure unique identifier:
Structure name: Sulton Ave OC
The fabricator/manufacturer/facility name: cemex

Material Information

The concrete mix design number: 1610887
The truck number from where the sample was collected: 10070485
The batch plant ticket number from where the sample was collected: 29559001
Concrete batch plant:
The fabricator/manufacturer designation for the sample: Cemex
A detailed description of where the material sample was collected: Center span at bent cap,bridge deck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 2

DIME Test ID: 2021-04-02-8-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 04/21/2021
Date Tested: 04/12/2021
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 28.27 in^2
Cross sectional area of cylinder 2 28.37 in^2
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength (to nearest 10 psi) 4420 psi
Average diameter of cylinder 1 6.00 in
Average diameter of cylinder 2 6.01 in
Compressive strength of cylinder 1 4375.7 psi
Compressive strength of cylinder 2 4457.3 psi
Maximum load on cylinder 1 123700 lb
Maximum load on cylinder 2 126455 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 10 days

Test 2 of 2

DIME Test ID: 2021-04-02-8-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 04/30/2021
Date Tested: 04/30/2021
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 28.37 in^2
Cross sectional area of cylinder 2 28.46 in^2
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength (to nearest 10 psi) 5130 psi
Average diameter of cylinder 1 6.01 in
Average diameter of cylinder 2 6.02 in
Compressive strength of cylinder 1 5019.9 psi
Compressive strength of cylinder 2 5231.4 psi
Maximum load on cylinder 1 142415 lb
Maximum load on cylinder 2 148885 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 28 days