Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 209175 DEA: 030F2204 EFIS: 0300000072
QA Service Level: 1
DIST-CO-RTE-PM: 03-ED-50-R30.7/R31.7
Work Description: REPLACE BRIDGE.
Location Description: SLY PARK UNDERCROSSING
Contractor Name: VIKING CONSTRUCTION COMPANY, INC.
Contractor Address: P.O. Box 1508 , Rancho Cordova, CA 95741
Resident Engineer: Jarrett Woodruff Structure Rep.: Brandon Miller
DIME Sample ID: 2014-04-24-11179795
TL Number from the TL Form:
Sample Submitted By Organization: Con-Fab California Corporation - Lathrop
Sample Organization Contact: (209) 249-4700
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 04/24/2014
Date that the sample was received by the laboratory/organization performing the testing: 04/24/2014
The quantity of what the sample constitutes: 2 cylinders
A brief description of the sample: PC concrete
From where was the sample collected: Source
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: ConFab
The concrete mix design number: 33333333
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: sdfgsdfdfg
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: bed 7
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2014-04-24-11179795-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 04/24/2014
Date Tested: 04/24/2014
Submitted By Organization: Con-Fab California Corporation - Lathrop
Organization Address: 1910 Lathrop Road,
Organization City: Lathrop
Organization State: CA
Organization Zipcode: 95330
Organization Email: dannyc@confabca.com
Organization Phone: (209) 249-4717
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
no data
|
Cross sectional area of cylinder 2
|
no data
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
5500 psi
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.00 in
|
Maximum load on cylinder 1
|
35000 lb
|
Maximum load on cylinder 2
|
35000 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
28 days
|