Sample Record for 2020-11-09-25
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 214543 DEA: 080K8404 EFIS: 0800020563
QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-L5726-
Work Description: MAINTENANCE STATION BUILDING WORK.
Location Description: SAN BERNARDINO AT THE SAN BERNARDINO MAINTENANCE STATION AT 175 WEST CLUSTER STREET
Contractor Name: PCN3 Inc.
Contractor Address: 5450 Katella Ave. #101, Los Alamitos, CA, 90720
Resident Engineer: Nicholas Mineo Structure Rep.: Tim Flores
Sample Information
DIME Sample ID: 2020-11-09-25
TL Number from the TL Form: 1
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 11/09/2020
Date that the sample was received by the laboratory/organization performing the testing: 11/23/2020
The quantity of what the sample constitutes: 3 CY
A brief description of the sample: Concrete Cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 1020-119
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Robertsons
Material Information
The concrete mix design number: SM445B37
The truck number from where the sample was collected: 1796
The batch plant ticket number from where the sample was collected: 5844371
Concrete batch plant: ROBERTSONS
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: LINE PUMP
Where the material sample would have been placed if not sampled: SHOP 8 BUILDING FOOTINGS
From Lot No.:
Bag Lot No.:
Test Results
Test 1 of 1
DIME Test ID: 2020-11-09-25-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 12/28/2020
Date Tested: 12/07/2020
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Average diameter of cylinder 1
|
5.99 in
|
Average diameter of cylinder 2
|
6.01 in
|
Cross sectional area of cylinder 1
|
28.18 in^2
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
Compressive strength (to nearest 10 psi)
|
4740 psi
|
Maximum load on cylinder 1
|
134530 lb
|
Maximum load on cylinder 2
|
133280 lb
|
Compressive strength of cylinder 1
|
4774.0 psi
|
Type of fracture pattern of cylinder 1
|
1
|
Compressive strength of cylinder 2
|
4697.9 psi
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
no data
|