Project ID: 213707 DEA: 081C38U4 EFIS: 0817000196
QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-10-6.7/R25.1
Work Description: Remove concrete pavement and base, and place HMA and JPCP
Location Description: ROUTE 10/60 SEPARATION IN BEAUMONT TO ROUTE 10/111 SEPARATION NEAR CABAZON.
Contractor Name: Coffman Specialties
Contractor Address: 9685 Via Excelencia, San Diego, CA 92126
Resident Engineer: Elvira Lenart Structure Rep.: Unknown
DIME Sample ID: 2020-11-01-5
TL Number from the TL Form:
Sample Submitted By Organization: CT D08 - Fontana Field Testing Laboratory
Sample Organization Contact: 9512323690
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 11/01/2020
Date that the sample was received by the laboratory/organization performing the testing: 11/02/2020
The quantity of what the sample constitutes: 4 Beams
A brief description of the sample: JPCP beams
From where was the sample collected: Job Site
Laboratory sample identification: 1IA1, 1IA2, 1IB1, 1IB2
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Coffman Specialties, Inc
The concrete mix design number: 1906-2 R3
The truck number from where the sample was collected: Unknown
The batch plant ticket number from where the sample was collected: tt
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: Discharge from concrete truck into wheelbarrow
Where the material sample would have been placed if not sampled: Unknown
From Lot No.: Unknown
Bag Lot No.: Unknown
DIME Test ID: 2020-11-01-5-1
Test Method: CTM 523-July 2012: Method of Test for Flexural Strength of Concrete
Verified Date: 11/30/2020
Date Tested: 11/06/2020
Submitted By Organization: CT D08 - Fontana Field Testing Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: prakash.gowda@dot.ca.gov
Organization Phone: (951) 232-3690
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
What test method is being used?
|
Third-Point Loading
|
Fracture initiates in the tension surface
|
Within the Middle Third of the Span Length
|
Modulus of rupture
|
560 psi
|
DIME Test ID: 2020-11-01-5-2
Test Method: CTM 523-July 2012: Method of Test for Flexural Strength of Concrete
Verified Date: 11/30/2020
Date Tested: 11/06/2020
Submitted By Organization: CT D08 - Fontana Field Testing Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: prakash.gowda@dot.ca.gov
Organization Phone: (951) 232-3690
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
What test method is being used?
|
Center-Point Loading
|
Fracture initiates in the tension surface
|
Within the Middle Third of the Span Length
|
Modulus of rupture
|
590 psi
|
DIME Test ID: 2020-11-01-5-3
Test Method: CTM 504-June 2010: Method of Test for Determining Air Content of Freshly Mixed Concrete by the Pressure Method
Verified Date: 11/30/2020
Date Tested: 11/01/2020
Submitted By Organization: CT D08 - Fontana Field Testing Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: prakash.gowda@dot.ca.gov
Organization Phone: (951) 232-3690
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
DIME Test ID: 2020-11-01-5-4
Test Method: CTM 533-June 2010: Method of Test for Ball Penetration in Fresh Portland Cement Concrete
Verified Date: 11/30/2020
Date Tested: 11/01/2020
Submitted By Organization: CT D08 - Fontana Field Testing Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: prakash.gowda@dot.ca.gov
Organization Phone: (951) 232-3690
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Ball penetration in freshly mixed concrete (average)
|
1.75 inch
|
DIME Test ID: 2020-11-01-5-5
Test Method: CTM 518-June 2010: Method of Test for Unit Weight of Fresh Concrete
Verified Date: 11/30/2020
Date Tested: 11/01/2020
Submitted By Organization: CT D08 - Fontana Field Testing Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: prakash.gowda@dot.ca.gov
Organization Phone: (951) 232-3690
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit weight of the concrete
|
141.7 lb/ft^3
|
Cement content
|
587 lb/yd^3
|
DIME Test ID: 2020-11-01-5-6
Test Method: CTM 523-July 2012: Method of Test for Flexural Strength of Concrete
Verified Date: 11/30/2020
Date Tested: 11/29/2020
Submitted By Organization: CT D08 - Fontana Field Testing Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: prakash.gowda@dot.ca.gov
Organization Phone: (951) 232-3690
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
What test method is being used?
|
Third-Point Loading
|
Fracture initiates in the tension surface
|
Within the Middle Third of the Span Length
|
Modulus of rupture
|
570 psi
|
DIME Test ID: 2020-11-01-5-7
Test Method: CTM 523-July 2012: Method of Test for Flexural Strength of Concrete
Verified Date: 11/30/2020
Date Tested: 11/29/2020
Submitted By Organization: CT D08 - Fontana Field Testing Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: prakash.gowda@dot.ca.gov
Organization Phone: (951) 232-3690
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
What test method is being used?
|
Third-Point Loading
|
Fracture initiates in the tension surface
|
Within the Middle Third of the Span Length
|
Modulus of rupture
|
580 psi
|