Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 213747 DEA: 080Q9104 EFIS: 0800020580
QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-10-R23.8
Work Description: RETROFIT BRIDGE PIER WALLS, FOOTINGS AND POLYESTER CONCRETE OVERLAY.
Location Description: SAN BERNARDINO COUNTY IN COLTON AT THE SANTA ANA RIVER BRIDGES
Contractor Name: PETERSON-CHASE GENERAL ENGINEERING CONSTRUCTION, INC.
Contractor Address: 16351 Construction Circle West, Irvine, CA 92606-4414
Resident Engineer: Roberto Castro Structure Rep.: Ching Chuang
DIME Sample ID: 2020-09-23-34
TL Number from the TL Form: 1017-23
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 09/23/2020
Date that the sample was received by the laboratory/organization performing the testing: 10/01/2020
The quantity of what the sample constitutes: Set of Cylinders
A brief description of the sample: Concrete Cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 1017-23
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: NA
The concrete mix design number: NOT PROVIDED
The truck number from where the sample was collected: Unknown
The batch plant ticket number from where the sample was collected: Unknown
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Unknown
Where the material sample would have been placed if not sampled: Str Conc Bridge Footing Pier 8QR
From Lot No.:
Bag Lot No.:
DIME Test ID: 2020-09-23-34-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 10/27/2020
Date Tested: 10/21/2020
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.02 in
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.46 in^2
|
Compressive strength (to nearest 10 psi)
|
5320 psi
|
Maximum load on cylinder 1
|
151060 lb
|
Maximum load on cylinder 2
|
150720 lb
|
Compressive strength of cylinder 1
|
5343.5 psi
|
Type of fracture pattern of cylinder 1
|
2
|
Compressive strength of cylinder 2
|
5295.9 psi
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
no data
|