Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 210673 DEA: 042640F4 EFIS: 0400020132 COOP: 042308A3
QA Service Level: 1
DIST-CO-RTE-PM: 04-SON--
Work Description:
Location Description:
Contractor Name: GHILOTTI CONSTRUCTION CO. INC.
Contractor Address: 246 GHILOTTI AVENUE, SANTA ROSA, CA 95407
Resident Engineer: Gina Choi Structure Rep.: Brian Beaudoin
DIME Sample ID: 2020-10-12-8
TL Number from the TL Form: C918529
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (916) 227-7253
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 10/12/2020
Date that the sample was received by the laboratory/organization performing the testing: 10/13/2020
The quantity of what the sample constitutes: 4
A brief description of the sample: Erico Lenton Stander A2 Couplers
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: cascade Erico Lenton PSO Reinforcing
Production or Authorization Testing: Production Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: Cascade nucor
Coupler Manufacturer: Erico Lenton
Intermediate Assembler or Fabricator:
Rebar Size: #8
Coupler Model: Lenton A2
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): L9711
Rebar Heat Number(s): 3500010655
Rebar Size 2 :
Coupler Unique ID:
DIME Test ID: 2020-10-12-8-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 10/15/2020
Date Tested: 10/14/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: 916-227-7257
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 1 | | No. 8/25mm | 1 | -0.0006 | 0.79 | 75955 | 96145 | Service Splice | fsaylor |
| |
UTM
|
400kip
|
Temperature
|
72.00 f
|
Halo ID
|
Small
|
DIME Test ID: 2020-10-12-8-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 10/15/2020
Date Tested: 10/14/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: 916-227-7257
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 2 | | No. 8/25mm | 1 | 0 | 0.79 | 76164 | 96410 | Service Splice | fsaylor |
| |
UTM
|
400kip
|
Temperature
|
72.00 f
|
Halo ID
|
|
DIME Test ID: 2020-10-12-8-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 10/15/2020
Date Tested: 10/14/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: 916-227-7257
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 3 | | No. 8/25mm | 1 | 0 | 0.79 | 74674 | 94524 | Service Splice | fsaylor |
| |
UTM
|
400kip
|
Temperature
|
72.00 f
|
Halo ID
|
|