Sample Record for 2020-07-08-32
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 214756 DEA: 050N7AU4 EFIS: 0520000030
QA Service Level: 1
DIST-CO-RTE-PM: 05-SB-101-1.4/4.8
Work Description: Segment 4A - Carpinteria: Construct HOV lanes and rehabilitation. Source inspection of sign structure trusses, lighting structures, epoxy coated rebar, precast box culverts, precast RCP.
Location Description: CARPINTERIA FROM 0.2 MILE SOUTH OF BAILARD AVENUE OVERCROSSING TO 0.7 MILE SOUTH OF SOUTH PADARO LANE
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: 5335 Debbie Rd, Santa Barbara, CA 93160
Resident Engineer: Taylor Merlo Structure Rep.: Bernardo Hernandez
Sample Information
DIME Sample ID: 2020-07-08-32
TL Number from the TL Form: na
Sample Submitted By Organization: Rinker Materials
Sample Organization Contact: (916) 381-3910
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 07/08/2020
Date that the sample was received by the laboratory/organization performing the testing: 07/07/2020
The quantity of what the sample constitutes: 8 6X12 CYLINDERS
A brief description of the sample: Concrete Test Samples
From where was the sample collected: Fabricator
Laboratory sample identification: 7-8 box
Structure unique identifier: 36-0000
Structure name: Highway 132
The fabricator/manufacturer/facility name: Forterra Pipe and Precast, Florin Rd
Material Information
The concrete mix design number: 5H
The truck number from where the sample was collected: NA
The batch plant ticket number from where the sample was collected: 141651
Concrete batch plant: Forterra Florin Rd
The fabricator/manufacturer designation for the sample: batch
A detailed description of where the material sample was collected: conveyor belt
Where the material sample would have been placed if not sampled: RCBC
From Lot No.: NA
Bag Lot No.: NA
Test Results
Test 1 of 3
DIME Test ID: 2020-07-08-32-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 08/08/2020
Date Tested: 07/10/2020
Submitted By Organization: Rinker Materials
Organization Address: 7020 Tokay Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95828
Organization Email: Edgar.Benitez@Rinkerpipe.com
Organization Phone: (209) 401-6972
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C1231
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.00 in
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Compressive strength (to nearest 10 psi)
|
3580 psi
|
Maximum load on cylinder 1
|
100390 lb
|
Maximum load on cylinder 2
|
102165 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
2 days
|
Age of specimen in hours
|
48 hours
|
Test 2 of 3
DIME Test ID: 2020-07-08-32-2
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 08/08/2020
Date Tested: 07/15/2020
Submitted By Organization: Rinker Materials
Organization Address: 7020 Tokay Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95828
Organization Email: Edgar.Benitez@Rinkerpipe.com
Organization Phone: (209) 401-6972
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C1231
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.00 in
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Compressive strength (to nearest 10 psi)
|
4940 psi
|
Maximum load on cylinder 1
|
139580 lb
|
Maximum load on cylinder 2
|
139645 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
7 days
|
Age of specimen in hours
|
168 hours
|
Test 3 of 3
DIME Test ID: 2020-07-08-32-3
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 08/08/2020
Date Tested: 08/05/2020
Submitted By Organization: Rinker Materials
Organization Address: 7020 Tokay Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95828
Organization Email: Edgar.Benitez@Rinkerpipe.com
Organization Phone: (209) 401-6972
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.00 in
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Compressive strength (to nearest 10 psi)
|
6760 psi
|
Maximum load on cylinder 1
|
189240 lb
|
Maximum load on cylinder 2
|
192670 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
672 hours
|