Sample Record for 2020-07-28-7
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 213737 DEA: 07289104 EFIS: 0700021123
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-405-11.9/13.2
Work Description: Rehabilitate the existing Commercial Vehicle Enforcement Facility.
Location Description: LOS ANGELES COUNTY IN CARSON FROM DEL AMO BOULEVARD OVER CROSSING TO VERMONT AVENUE (190TH) UNDER CROSSING.
Contractor Name: POWELL CONSTRUCTORS, INC.
Contractor Address: 8555 Banana Avenue, Fontana, CA 92335
Resident Engineer: Samuel Gallardo Structure Rep.: Bernabe Contreras Jr
Sample Information
DIME Sample ID: 2020-07-28-7
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Sacramento Field Office
Sample Organization Contact: (916) 2058871
Type of Sample: Quality Assurance
Type of Material: SMTL TM3 - Fastener Assembly
Sample Taken Date: 07/28/2020
Date that the sample was received by the laboratory/organization performing the testing: 07/31/2020
The quantity of what the sample constitutes: 28
A brief description of the sample: 5/8-11x4 1/2" A325 HVY HX Bolts, Plain
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Nucor
Material Information
Rocap Number(s): B385001A N425659A WD8070
Heat Number(s): 100785790
Nut Mfg. Lot Number(s): n/a
Washer Mfg. Lot Number(s): n/a
Bolt Specification: ASTM A325
Bolt Length(s): 4 1/2"
Nut Specification: n/a
Washer Specification: n/a
Finish: Plain
Diameter/Size: 5/8-11"
Bolt Mfg. Lot Number: 385001A
Rocap Test Requirement(s):
Lubricant Requirements(s):
Test Results
Test 1 of 2
DIME Test ID: 2020-07-28-7-1
Test Method: ASTM F606-14a: Standard Test Methods for Determining the Mechanical Properties of Externally and Internally Threaded Fasteners, Washers, Direct Tension Indicators, and Rivets (Proof Load with Wedge)
Verified Date: 08/06/2020
Date Tested: 08/03/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: A325 Wedge Tensile
Test Result Compliance:
Additional Comments When Verified:
Number of Bolt Samples
|
1
|
Sample | Bolt Mfg. Lot Number | Size (in) | Peak Load (lbf) | Peak Load (kN) | Wedge Angle (deg) | Comments | Tested By | 1A | 385001A | 0.6250 | 31952 | 142.13 | 10.00 | A325 Wedge Tensile | spaine |
| |
UTM
|
450kip
|
Temperature
|
no data
|
Test 2 of 2
DIME Test ID: 2020-07-28-7-2
Test Method: ASME B1.2-83r01: (Ring Gage) Gages and Gaging for Unified Inch Screw Threads - Errata May 1992 (Ring Gage)
Verified Date: 08/06/2020
Date Tested: 08/05/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Sample No.
|
1A
|
Rocap Number
|
no data
|
Heat Number(s)
|
no data
|
Mfg. Lot Number
|
385001A
|
Finish Coating
|
Plain
|
Product Markings
|
A325 N
|
Size
|
.625 in
|
Bolt Length
|
4.5 in
|
Gage Type
|
Pass
|