Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 8801 DEA: AML-CEM EFIS: AML-CEM
QA Service Level:
DIST-CO-RTE-PM: 59---
Work Description: Special project for Cementitious Materials for use in Concrete Authorized Material List (AML)
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown
DIME Sample ID: 2020-07-15-22
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Sample Organization Contact: (916) 227-7071
Type of Sample: Annual Source Testing
Type of Material: Cementitious
Sample Taken Date: 07/15/2020
Date that the sample was received by the laboratory/organization performing the testing: 07/15/2020
The quantity of what the sample constitutes: 1 Bucket
A brief description of the sample: Class F Flyash
From where was the sample collected: Source
Laboratory sample identification: CM205045
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: ENX
DIME Test ID: 2020-07-15-22-2
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 08/18/2021
Date Tested: 11/16/2020
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 7 day test
Test Result Compliance: does not comply
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
yes
|
Age of specimen
|
7 days
|
The amount of flow
|
114 %
|
The amount of water used
|
46.0 %
|
Compressive strength of 1st specimen
|
3393 psi
|
Compressive strength of 2nd specimen
|
3238 psi
|
Compressive strength of 3rd specimen
|
3324 psi
|
Average Compressive strength (to nearest 10 psi)
|
3320 psi
|
Average Compressive strength (to nearest 10 psi) control group
|
4480 psi
|
Strength Activity Index of Portland Cement per ASTM C109
|
74 %
|
DIME Test ID: 2020-07-15-22-3
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 08/18/2021
Date Tested: 12/07/2020
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 28 day test -- Specimen 3 was eliminated from the average for being outside allowable limits per Section 12 of ASTM C109
Test Result Compliance: does not comply
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
yes
|
Age of specimen
|
28 days
|
The amount of flow
|
114 %
|
The amount of water used
|
46.0 %
|
Compressive strength of 1st specimen
|
4409 psi
|
Compressive strength of 2nd specimen
|
4303 psi
|
Compressive strength of 3rd specimen
|
0 psi
|
Average Compressive strength (to nearest 10 psi)
|
4360 psi
|
Average Compressive strength (to nearest 10 psi) control group
|
5920 psi
|
Strength Activity Index of Portland Cement per ASTM C109
|
74 %
|
DIME Test ID: 2020-07-15-22-4
Test Method: ASTM C430-8: Standard Test Method for Fineness of Hydraulic Cement by the 45-μm (No. 325) Sieve
Verified Date: 08/18/2021
Date Tested: 10/30/2020
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Correction Factor (CF)
|
.31
|
Corrected Residue (Rc)
|
20.5
|
DIME Test ID: 2020-07-15-22-5
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 08/18/2021
Date Tested: 07/08/2021
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 7 day test
Test Result Compliance: complies
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
yes
|
Age of specimen
|
7 days
|
The amount of flow
|
117 %
|
The amount of water used
|
46.0 %
|
Compressive strength of 1st specimen
|
3716 psi
|
Compressive strength of 2nd specimen
|
4032 psi
|
Compressive strength of 3rd specimen
|
3985 psi
|
Average Compressive strength (to nearest 10 psi)
|
3910 psi
|
Average Compressive strength (to nearest 10 psi) control group
|
4600 psi
|
Strength Activity Index of Portland Cement per ASTM C109
|
85 %
|
DIME Test ID: 2020-07-15-22-6
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 08/18/2021
Date Tested: 07/29/2021
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 28 day test -- Specimen 1 was eliminated from the average for being outside allowable limits per Section 12 of ASTM C109
Test Result Compliance: complies
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
yes
|
Age of specimen
|
28 days
|
The amount of flow
|
117 %
|
The amount of water used
|
46.0 %
|
Compressive strength of 1st specimen
|
5397 psi
|
Compressive strength of 2nd specimen
|
4878 psi
|
Compressive strength of 3rd specimen
|
4822 psi
|
Average Compressive strength (to nearest 10 psi)
|
4850 psi
|
Average Compressive strength (to nearest 10 psi) control group
|
5530 psi
|
Strength Activity Index of Portland Cement per ASTM C109
|
88 %
|