Print Report | Back to Sample Detail

Sample Record for 2020-05-11-1

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 213229 DEA: 050A0504 EFIS: 0500000007 QA Service Level: 1
DIST-CO-RTE-PM: 05-SB-1-15.6
Work Description: BRIDGE REPLACEMENT, RETAINING WALL AND FISH PASSAGE.
Location Description: SANTA BARBARA COUNTY NEAR LOMPOC AT SALSIPUEDES CREEK BRIDGE
Contractor Name: Cal Portland Construction
Contractor Address: 1625 E DONOVAN RD, SANTA MARIA, CA 93454
Resident Engineer: Lilian Bennetzen Structure Rep.: Bernardo Hernandez

Sample Information

DIME Sample ID: 2020-05-11-1
TL Number from the TL Form: C970819
Sample Submitted By Organization: CT HQ - QASI Sacramento Field Office
Sample Organization Contact: (916) 2058871
Type of Sample: Acceptance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 05/11/2020
Date that the sample was received by the laboratory/organization performing the testing: 05/14/2020
The quantity of what the sample constitutes: 30
A brief description of the sample: #5 Bar-Lock Mechanical Couplers
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Pacific Steel Goup

Material Information

Production or Authorization Testing: Authorization Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: Nucor
Coupler Manufacturer: Dayton Supior Corp
Intermediate Assembler or Fabricator: Pacific Steel Group
Rebar Size: #5
Coupler Model: D250 Bar Lock L-Series Type 2
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter: Unknown
Rebar Hoop Fabricator: Unknown
Coupler Component Heat/Lot Number(s): heat - MM18108718,A195032 Lot - 179538
Rebar Heat Number(s): 3500008748
Rebar Size 2 : 5
Coupler Unique ID:

Test Results

Test 1 of 3

DIME Test ID: 2020-05-11-1-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 05/19/2020
Date Tested: 05/18/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested 1
SampleNumber of CyclesSizeMfg. Lot Number(s)Slip (inch)Area (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
1No. 5/16mm1-0.00140.312859692247Service Splicebewing
UTM 400kip
Temperature 72.00 f
Halo ID Small

Test 2 of 3

DIME Test ID: 2020-05-11-1-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 05/19/2020
Date Tested: 05/18/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested 1
SampleNumber of CyclesSizeMfg. Lot Number(s)Slip (inch)Area (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
2No. 5/16mm100.312859692246Service Splicebewing
UTM 400kip
Temperature 72.00 f
Halo ID

Test 3 of 3

DIME Test ID: 2020-05-11-1-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 05/19/2020
Date Tested: 05/18/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested 1
SampleNumber of CyclesSizeMfg. Lot Number(s)Slip (inch)Area (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
3No. 5/16mm100.312864792408Service Splicebewing
UTM 400kip
Temperature 72.00 f
Halo ID