Sample Record for 2020-04-10-3

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 213411 DEA: 030H10U4 EFIS: 0317000246 QA Service Level: 1
DIST-CO-RTE-PM: 03-SAC-5-9.7/24.9
Work Description:
Location Description: Construction on state highway in Sacramento County in and near Sacramento from 1.1 miles south of Elk Grove Boulevard to American River Viaduct
Contractor Name: NOR CAL PAVING TEICHERT/GRANITE
Contractor Address: 400 Sunrise Ave. Ste. #300, Roseville, CA 95661
Resident Engineer: Daniel Tecle Structure Rep.: Pha Tran

Sample Information

DIME Sample ID: 2020-04-10-3
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Sacramento Field Office
Sample Organization Contact: (916) 2058871
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Headed Bars
Sample Taken Date: 04/10/2020
Date that the sample was received by the laboratory/organization performing the testing: 04/22/2020
The quantity of what the sample constitutes: 2,160
A brief description of the sample: HRC 555 Headed Reinforcement
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Camblin Steel Service, Benicia

Material Information

Production or Authorization Testing: Production Testing
Rebar Heat Number(s): 067220
Head Manufacturer Lot Number(s): 1 through 15
Rebar Size: #6
Headed Bar Model Name: HRC 555
Size of Head: Reduced Size - 4x
Head Connection Type: Inertia Weld
Head Shape: Circular
Rebar Manufacturer: Cascade Steel
Head Manufacturer: Camblin Steel Service
Head Fabricator: Camblin Steel Service
Material Standard Code: ASTM A706
Headed Bar Unique ID:

Test Results

Test 1 of 12

DIME Test ID: 2020-04-10-3-1
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/16/2020
Date Tested: 04/14/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
10.444344498737Ok Neckingbewing
Temperature 72 f
UTM 400kip

Test 2 of 12

DIME Test ID: 2020-04-10-3-2
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/16/2020
Date Tested: 04/14/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
10.444354498964Ok Neckingbewing
Temperature 72 f
UTM 400kip

Test 3 of 12

DIME Test ID: 2020-04-10-3-3
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/16/2020
Date Tested: 04/14/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
10.444351398892Ok Neckingbewing
Temperature 72 f
UTM 400kip

Test 4 of 12

DIME Test ID: 2020-04-10-3-4
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/16/2020
Date Tested: 04/14/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
40.444358599058Ok Neckingbewing
Temperature 72 f
UTM 400kip

Test 5 of 12

DIME Test ID: 2020-04-10-3-5
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/16/2020
Date Tested: 04/14/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
40.444347298801Ok Neckingbewing
Temperature 72 f
UTM 400kip

Test 6 of 12

DIME Test ID: 2020-04-10-3-6
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/16/2020
Date Tested: 04/14/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
40.444355598989Ok Neckingbewing
Temperature 72 f
UTM 400kip

Test 7 of 12

DIME Test ID: 2020-04-10-3-7
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/16/2020
Date Tested: 04/14/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
90.444346098772Ok Neckingbewing
Temperature 72 f
UTM 400kip

Test 8 of 12

DIME Test ID: 2020-04-10-3-8
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/16/2020
Date Tested: 04/14/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
90.444363299164Ok Neckingbewing
Temperature 72 f
UTM 400kip

Test 9 of 12

DIME Test ID: 2020-04-10-3-9
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/16/2020
Date Tested: 04/14/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
90.444395999906Ok Neckingbewing
Temperature 72 f
UTM 400kip

Test 10 of 12

DIME Test ID: 2020-04-10-3-10
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/16/2020
Date Tested: 04/14/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
140.444338498600Ok Neckingbewing
Temperature 72 f
UTM 400kip

Test 11 of 12

DIME Test ID: 2020-04-10-3-11
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/16/2020
Date Tested: 04/14/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
140.444350498874Ok Neckingbewing
Temperature 72 f
UTM 400kip

Test 12 of 12

DIME Test ID: 2020-04-10-3-12
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/16/2020
Date Tested: 04/14/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
140.4444243100553Ok Neckingbewing
Temperature 72 f
UTM 400kip