Project ID: 213746 DEA: 080Q75U4 EFIS: 0817000114
QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD,RIV-60-R4.6/R9.9, R0.0/12.2
Work Description: REPLACEMENT OF TWO OUTSIDE LANES AND CONCRETE SLABS
Location Description:
Contractor Name: J McLoughlin Engineering
Contractor Address: 10641 Fulton Court, Rancho Cucamonga, CA 91730
Resident Engineer: Mujahid Qureshi Structure Rep.: Ching Chuang
DIME Sample ID: 2020-03-03-19
TL Number from the TL Form: 999-303B
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 03/03/2020
Date that the sample was received by the laboratory/organization performing the testing: 03/04/2020
The quantity of what the sample constitutes: 2 Cylinders
A brief description of the sample: 6x12 LCB cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 999-303B
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: NA
The concrete mix design number: LCB-60
The truck number from where the sample was collected: NA
The batch plant ticket number from where the sample was collected: NA
Concrete batch plant: NA
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: Job Site
Where the material sample would have been placed if not sampled: EB RTE 60 EAST OF ARCHIBALD ON LANE 3 AND 4 sta 41810 to 42720
From Lot No.: Unknown
Bag Lot No.: Unknown
DIME Test ID: 2020-03-03-19-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 03/12/2020
Date Tested: 03/10/2020
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.01 in
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
Compressive strength (to nearest 10 psi)
|
830 psi
|
Maximum load on cylinder 1
|
23910 lb
|
Maximum load on cylinder 2
|
22910 lb
|
Compressive strength of cylinder 1
|
845.8 psi
|
Type of fracture pattern of cylinder 1
|
2
|
Compressive strength of cylinder 2
|
807.5 psi
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
7 days
|
Age of specimen in hours
|
no data
|