Print Report | Back to Sample Detail

Sample Record for 2020-01-23-10

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 210837 DEA: 080J0804 EFIS: 0800000283 COOP: 081625 QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-15-34.7/51.6
Work Description: (Alternative Delivery) DESIGN-BUILD OF THE INTERSTATE 15 EXPRESS LANES PROJECT
Location Description: Riverside County and SBD-15-0.0/1.3
Contractor Name: Skanska-Ames, Joint Venture
Contractor Address: 1801 California Avenue, Corona, CA 92881
Resident Engineer: Roy Fisher (reports) Structure Rep.: Roy Fisher

Sample Information

DIME Sample ID: 2020-01-23-10
TL Number from the TL Form: 151
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 01/23/2020
Date that the sample was received by the laboratory/organization performing the testing: 01/27/2020
The quantity of what the sample constitutes: 6 concrete cylinders
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 974-151
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Robertsons

Material Information

The concrete mix design number: SC590B39
The truck number from where the sample was collected: 1669
The batch plant ticket number from where the sample was collected: 4948944
Concrete batch plant: Robertsons
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: Load 9 @ 90 cu yd
Where the material sample would have been placed if not sampled: Hidden Valley Parkway NB Onramp RW8 Footing Norco Segment
From Lot No.: Unknown
Bag Lot No.: Unknown

Test Results

Test 1 of 2

DIME Test ID: 2020-01-23-10-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 02/06/2020
Date Tested: 02/06/2020
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 6.01 in
Average diameter of cylinder 2 6.01 in
Cross sectional area of cylinder 1 28.37 in^2
Cross sectional area of cylinder 2 28.37 in^2
Compressive strength (to nearest 10 psi) 4180 psi
Maximum load on cylinder 1 117340 lb
Maximum load on cylinder 2 119910 lb
Compressive strength of cylinder 1 4136.1 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 4226.6 psi
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 14 days
Age of specimen in hours no data

Test 2 of 2

DIME Test ID: 2020-01-23-10-2
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 02/21/2020
Date Tested: 02/20/2020
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 6.00 in
Average diameter of cylinder 2 6.01 in
Cross sectional area of cylinder 1 28.27 in^2
Cross sectional area of cylinder 2 28.37 in^2
Compressive strength (to nearest 10 psi) 4890 psi
Maximum load on cylinder 1 137000 lb
Maximum load on cylinder 2 140210 lb
Compressive strength of cylinder 1 4846.1 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 4942.2 psi
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 28 days
Age of specimen in hours no data