Print Report | Back to Sample Detail

Sample Record for 2020-01-03-1

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 210837 DEA: 080J0804 EFIS: 0800000283 COOP: 081625 QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-15-34.7/51.6
Work Description: (Alternative Delivery) DESIGN-BUILD OF THE INTERSTATE 15 EXPRESS LANES PROJECT
Location Description: Riverside County and SBD-15-0.0/1.3
Contractor Name: Skanska-Ames, Joint Venture
Contractor Address: 1801 California Avenue, Corona, CA 92881
Resident Engineer: Roy Fisher (reports) Structure Rep.: Roy Fisher

Sample Information

DIME Sample ID: 2020-01-03-1
TL Number from the TL Form: 146
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 01/03/2020
Date that the sample was received by the laboratory/organization performing the testing: 01/06/2020
The quantity of what the sample constitutes: 6 cylinders
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 974-146
Structure unique identifier:
Structure name: Parkridge UC LT Barrier Rail Left
The fabricator/manufacturer/facility name: Robertsons

Material Information

The concrete mix design number: SC590B39
The truck number from where the sample was collected: 1980
The batch plant ticket number from where the sample was collected: 5105441
Concrete batch plant: Robertsons
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: Load 1 at 10 Cubic Yards
Where the material sample would have been placed if not sampled: Parkridge UC LT Barrier Rail Left
From Lot No.: Unknown
Bag Lot No.: Unknown

Test Results

Test 1 of 3

DIME Test ID: 2020-01-03-1-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 02/01/2020
Date Tested: 01/17/2020
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 28.37 in^2
Cross sectional area of cylinder 2 28.37 in^2
Capped in accordance with? ASTM C617/CTM521
Compressive strength (to nearest 10 psi) 3200 psi
Average diameter of cylinder 1 6.01 in
Average diameter of cylinder 2 6.01 in
Compressive strength of cylinder 1 3141.0 psi
Compressive strength of cylinder 2 3251.7 psi
Maximum load on cylinder 1 89110 lb
Maximum load on cylinder 2 92250 lb
Type of fracture pattern of cylinder 1 1
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 14 days

Test 2 of 3

DIME Test ID: 2020-01-03-1-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 213-792-4794
This test has been superseded on 02/01/2020.
Reason: corrected

Test 3 of 3

DIME Test ID: 2020-01-03-1-3
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 02/03/2020
Date Tested: 01/31/2020
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 28.37 in^2
Cross sectional area of cylinder 2 28.27 in^2
Capped in accordance with? ASTM C617/CTM521
Compressive strength (to nearest 10 psi) 4320 psi
Average diameter of cylinder 1 6.01 in
Average diameter of cylinder 2 6.00 in
Compressive strength of cylinder 1 4232.6 psi
Compressive strength of cylinder 2 4414.2 psi
Maximum load on cylinder 1 120080 lb
Maximum load on cylinder 2 124790 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 28 days