Print Report | Back to Sample Detail

Sample Record for 2019-11-15-39

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 210837 DEA: 080J0804 EFIS: 0800000283 COOP: 081625 QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-15-34.7/51.6
Work Description: (Alternative Delivery) DESIGN-BUILD OF THE INTERSTATE 15 EXPRESS LANES PROJECT
Location Description: Riverside County and SBD-15-0.0/1.3
Contractor Name: Skanska-Ames, Joint Venture
Contractor Address: 1801 California Avenue, Corona, CA 92881
Resident Engineer: Roy Fisher (reports) Structure Rep.: Roy Fisher

Sample Information

DIME Sample ID: 2019-11-15-39
TL Number from the TL Form: 131
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 11/15/2019
Date that the sample was received by the laboratory/organization performing the testing: 11/18/2019
The quantity of what the sample constitutes: 4
A brief description of the sample: Concrete Cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 974-131
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Robertsons

Material Information

The concrete mix design number: SC590B39
The truck number from where the sample was collected: 1028
The batch plant ticket number from where the sample was collected: 4810938
Concrete batch plant: Robertsons
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: load 2
Where the material sample would have been placed if not sampled: riverside UC Rt Concrete Barrier
From Lot No.: Unknown
Bag Lot No.: Unknown

Test Results

Test 1 of 2

DIME Test ID: 2019-11-15-39-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 12/10/2019
Date Tested: 11/29/2019
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 6.01 in
Average diameter of cylinder 2 6.00 in
Cross sectional area of cylinder 1 28.37 in^2
Cross sectional area of cylinder 2 28.27 in^2
Compressive strength (to nearest 10 psi) 3750 psi
Maximum load on cylinder 1 105865 lb
Maximum load on cylinder 2 106555 lb
Compressive strength of cylinder 1 3731.6 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 3769.2 psi
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 14 days
Age of specimen in hours no data

Test 2 of 2

DIME Test ID: 2019-11-15-39-2
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 12/17/2019
Date Tested: 12/13/2019
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 6.01 in
Average diameter of cylinder 2 6.01 in
Cross sectional area of cylinder 1 28.37 in^2
Cross sectional area of cylinder 2 28.37 in^2
Compressive strength (to nearest 10 psi) 4380 psi
Maximum load on cylinder 1 125280 lb
Maximum load on cylinder 2 123150 lb
Compressive strength of cylinder 1 4415.9 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 4340.9 psi
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 28 days
Age of specimen in hours no data