Gavin Newsom, Governor |
DEPARTMENT OF TRANSPORTATIONDIVISION OF ENGINEERING SERVICES MATERIALS ENGINEERING AND TESTING SERVICES Concrete Materials Testing Branch 5900 Folsom Blvd. Sacramento, CA 95819 916-227-7205 |
Contract # 101L1504 Cty ALP Rte 89 PM 21.47, 21.46 Vendor # |
REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
Iqbal Aulakh |
Date Reported: |
11/06/2019 |
|
Address: |
TL Number: |
002 |
||
City: |
||||
Project Name: |
||||
Prime Contractor: Q&D Construction Inc. |
||||
Sample Taken Date: |
10/23/2019 |
Mix Design: |
1430CAL |
|
Contractor: Unknown |
Location: |
|||
Structure unique identifier: |
||||
Structure name: |
||||
Location of Pour: Unknown |
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 6.01 | 28.35 | 132311 | 4667.1 | 1 |
2 | 6.02 | 28.45 | 136869 | 4810.9 | 1 |
DIME Test ID: 2019-10-23-8-1
Number of specimens: 2
Compressive strength (to nearest 10 psi): 4740
Age of specimen: 14 days
Certified By: Larry McCrum
*Subject to final inspection by the Resident Engineer. |
TL- Report of Laboratory Testing