Sample Record for 2019-09-04-10
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 213856 DEA: 112888U4 EFIS: 1118000199
QA Service Level: 1
DIST-CO-RTE-PM: 11-SD-11,125,905-Various
Work Description: CONSTRUCT FREEWAY TO FREEWAY CONNECTORS AND 4-LANE HIGHWAY FACILITY
Location Description: SAN DIEGO COUNTY AT VARIOUS LOCATIONS
Contractor Name: Skanska USA Civil West CA
Contractor Address: 1995 Agua Mansa Road, Riverside, CA 92509
Resident Engineer: Carlos Covarrubias Structure Rep.: Wade Durant
Sample Information
DIME Sample ID: 2019-09-04-10
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (530) 329-6527
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Headed Bars
Sample Taken Date: 09/04/2019
Date that the sample was received by the laboratory/organization performing the testing: 10/16/2019
The quantity of what the sample constitutes: 8 of 225
A brief description of the sample: #14 10A Doughnut Headed Bars
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Integrity Rebar
Material Information
Production or Authorization Testing: Production Testing
Rebar Heat Number(s): 033695
Head Manufacturer Lot Number(s): A192336, MM18107398
Rebar Size: 14
Headed Bar Model Name: 10A Doughnut Taper
Size of Head: Full Size - 9x
Head Connection Type: Taper Threaded
Head Shape: Circular
Rebar Manufacturer: CMC Rebar
Head Manufacturer: Bar Splice
Head Fabricator: Integrity Rebar
Material Standard Code: ASTM A706
Headed Bar Unique ID:
Test Results
Test 1 of 6
DIME Test ID: 2019-09-04-10-1
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 10/17/2019
Date Tested: 10/17/2019
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke, Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 1 | 2.25 | 229697.49 | 102088 | Bar Broke, Ok Necking | bewing |
| |
Temperature
|
72 f
|
UTM
|
2000kip
|
Test 2 of 6
DIME Test ID: 2019-09-04-10-2
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 10/17/2019
Date Tested: 10/17/2019
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke, Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 1 | 2.25 | 227891.66 | 101285 | Bar Broke, Ok Necking | bewing |
| |
Temperature
|
72 f
|
UTM
|
2000kip
|
Test 3 of 6
DIME Test ID: 2019-09-04-10-3
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 10/17/2019
Date Tested: 10/17/2019
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke, Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 1 | 2.25 | 226562.70 | 100695 | Bar Broke, Ok Necking | bewing |
| |
Temperature
|
72 f
|
UTM
|
2000kip
|
Test 4 of 6
DIME Test ID: 2019-09-04-10-4
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 10/17/2019
Date Tested: 10/17/2019
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke, Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 2 | 2.25 | 224530.86 | 99791 | Bar Broke, Ok Necking | bewing |
| |
Temperature
|
72 f
|
UTM
|
2000kip
|
Test 5 of 6
DIME Test ID: 2019-09-04-10-5
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 10/17/2019
Date Tested: 10/17/2019
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke, Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 2 | 2.25 | 224559.26 | 99804 | Bar Broke, Ok Necking | bewing |
| |
Temperature
|
72 f
|
UTM
|
2000kip
|
Test 6 of 6
DIME Test ID: 2019-09-04-10-6
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 10/17/2019
Date Tested: 10/17/2019
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke, Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 2 | 2.25 | 224016.50 | 99563 | Bar Broke, Ok Necking | bewing |
| |
Temperature
|
72 f
|
UTM
|
2000kip
|