Project ID: 212687 DEA: 06442544 EFIS: 0612000175
QA Service Level: 1
DIST-CO-RTE-PM: 06-KER-46,5-31.5-33.2
Work Description: CONVERT 2-LANE TO 4-LANE CONVENTIONAL HIGHWAY.
Location Description: KERN COUNTY NEAR LOST HILLS FROM 1.0 MILE EAST OF LOST HILLS ROAD TO 0.7 MILE EAST OF ROUTE 46/5 SEPARATION
Contractor Name: SECURITY PAVING COMPANY, INC.
Contractor Address: 13170 TELFAIR AVENUE, SYLMAR, CA 91342
Resident Engineer: Amarjit Dhaliwal Structure Rep.: Ramandeep Guraya
DIME Sample ID: 2019-09-11-19
TL Number from the TL Form: NA
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (916) 227-7253
Type of Sample: Quality Assurance
Type of Material: SMTL TM3 - Fastener Assembly
Sample Taken Date: 09/11/2019
Date that the sample was received by the laboratory/organization performing the testing: 09/16/2019
The quantity of what the sample constitutes: 1
A brief description of the sample: F1554 Rod
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Gerdau
Rocap Number(s):
Heat Number(s): 58037789
Nut Mfg. Lot Number(s):
Washer Mfg. Lot Number(s):
Bolt Specification: F1554 Gr 55
Bolt Length(s): 29
Nut Specification: NA
Washer Specification: NA
Finish:
Diameter/Size: .75
Bolt Mfg. Lot Number:
Rocap Test Requirement(s):
Lubricant Requirements(s):
DIME Test ID: 2019-09-11-19-2
Test Method: ASTM F606-14: Standard Test Methods for Determining the Mechanical Properties of Externally and Internally Threaded Fasteners, Washers, Direct Tension Indicators, and Rivets (Hex Cap Screws)
Verified Date: 09/20/2019
Date Tested: 09/20/2019
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: 916-227-7257
General Comments for this Test: F1554 Rod
Test Result Compliance:
Additional Comments When Verified:
Number of Samples
|
1
|
Sample | Size | Area (in^2) | Peak Load (lbf) | Peak Load (kN) | Tensile Strength (psi) | Stress at Offset (psi) | Load at Offset (lbf) | Comments | 1 | 3/4 | 0.334 | 30766 | 136 | 92113 | 73128 | 24425 | F1554 Rod |
| |
UTM
|
400KIP
|
Temperature
|
72
|