Gavin Newsom, Governor |
DEPARTMENT OF TRANSPORTATIONDIVISION OF ENGINEERING SERVICES MATERIALS ENGINEERING AND TESTING SERVICES Concrete Materials Testing Branch 5900 Folsom Blvd. Sacramento, CA 95819 916-227-7205 |
Contract # 041J7004 Cty ALA Rte 123 PM 2.8 Vendor # |
REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
John Ruzic |
Date Reported: |
10/10/2019 |
|
Address: |
TL Number: |
290404 |
||
City: |
||||
Project Name: INSTALL TRAFFIC SIGNALS,WIDEN LEFT TURN LANES , CONSTRUCT CURB RAMPS |
||||
Prime Contractor: Columbia Electric |
||||
Sample Taken Date: |
09/11/2019 |
Mix Design: |
DDLSP8Q3 |
|
Contractor: Unknown |
Location : |
|||
Structure unique identifier: |
||||
Structure name: |
||||
Location of Pour: Unknown |
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 6.01 | 28.35 | 177891 | 6274.8 | 1 |
2 | 6.01 | 28.35 | 179742 | 6340.1 | 1 |
DIME Test ID: 2019-09-11-14-1
Number of specimens: 2
Compressive strength (to nearest 10 psi): 6310
Age of specimen: 28 days
Certified By: Larry McCrum
*Subject to final inspection by the Resident Engineer. |
![]() |
TL- Report of Laboratory Testing