Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 210837 DEA: 080J0804 EFIS: 0800000283 COOP: 081625
QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-15-34.7/51.6
Work Description: (Alternative Delivery) DESIGN-BUILD OF THE INTERSTATE 15 EXPRESS LANES PROJECT
Location Description: Riverside County and SBD-15-0.0/1.3
Contractor Name: Skanska-Ames, Joint Venture
Contractor Address: 1801 California Avenue, Corona, CA 92881
Resident Engineer: Roy Fisher (reports) Structure Rep.: Roy Fisher
DIME Sample ID: 2019-06-20-31
TL Number from the TL Form: 64
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 06/20/2019
Date that the sample was received by the laboratory/organization performing the testing: 07/24/2019
The quantity of what the sample constitutes: 6
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 974-64
Structure unique identifier:
Structure name: abutment 4
The fabricator/manufacturer/facility name: ROBERTSON CORONA
The concrete mix design number: rrm18094
The truck number from where the sample was collected: 2072
The batch plant ticket number from where the sample was collected: 4392753
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: load 4
Where the material sample would have been placed if not sampled: abutment 4
From Lot No.: Unknown
Bag Lot No.: Unknown
DIME Test ID: 2019-06-20-31-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 07/03/2019
Date Tested: 06/25/2019
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.37 in^2
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
3860 psi
|
Average diameter of cylinder 1
|
6.01 in
|
Average diameter of cylinder 2
|
6.01 in
|
Compressive strength of cylinder 1
|
3784.6 psi
|
Compressive strength of cylinder 2
|
3927.4 psi
|
Maximum load on cylinder 1
|
107370 lb
|
Maximum load on cylinder 2
|
111420 lb
|
Type of fracture pattern of cylinder 1
|
4
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
5 days
|
DIME Test ID: 2019-06-20-31-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 07/05/2019
Date Tested: 07/04/2019
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.37 in^2
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
5030 psi
|
Average diameter of cylinder 1
|
6.01 in
|
Average diameter of cylinder 2
|
6.01 in
|
Compressive strength of cylinder 1
|
5025.4 psi
|
Compressive strength of cylinder 2
|
5041.2 psi
|
Maximum load on cylinder 1
|
142570 lb
|
Maximum load on cylinder 2
|
143020 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
14 days
|
DIME Test ID: 2019-06-20-31-3
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 07/19/2019
Date Tested: 07/18/2019
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.46 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
5710 psi
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.02 in
|
Compressive strength of cylinder 1
|
5742.1 psi
|
Compressive strength of cylinder 2
|
5670.1 psi
|
Maximum load on cylinder 1
|
162330 lb
|
Maximum load on cylinder 2
|
161370 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Type of fracture pattern of cylinder 2
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
28 days
|