Project Information

Project ID: 212687 DEA: 06442544 EFIS: 0612000175 QA Service Level: 1
DIST-CO-RTE-PM: 06-KER-46,5-31.5-33.2
Work Description: CONVERT 2-LANE TO 4-LANE CONVENTIONAL HIGHWAY.
Location Description: KERN COUNTY NEAR LOST HILLS FROM 1.0 MILE EAST OF LOST HILLS ROAD TO 0.7 MILE EAST OF ROUTE 46/5 SEPARATION
Contractor Name: SECURITY PAVING COMPANY, INC.
Contractor Address: 13170 TELFAIR AVENUE, SYLMAR, CA 91342
Resident Engineer: Amarjit Dhaliwal Structure Rep.: Ramandeep Guraya

Sample Information

DIME Sample ID: 2019-06-26-1
TL Number from the TL Form: Unknown
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Headed Bars
Sample Taken Date: 06/26/2019
Date that the sample was received by the laboratory/organization performing the testing: 07/01/2019
The quantity of what the sample constitutes: 16
A brief description of the sample: HRC 555 T-Heads
From where was the sample collected: Fabricator
Laboratory sample identification: Unknown
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: CMC San Bernardino

Material Information

Production or Authorization Testing: Production Testing
Rebar Heat Number(s): 6503153102
Head Manufacturer Lot Number(s): 3
Rebar Size: 9
Headed Bar Model Name: 555 T Heads
Size of Head: Reduced Size - 4x
Head Connection Type: Forged
Head Shape: Circular
Rebar Manufacturer: Gerdau
Head Manufacturer: Gerdau RSW
Head Fabricator: Gerdau HRC
Material Standard Code: ASTM A706
Headed Bar Unique ID:

Test Results

Test 1 of 3

DIME Test ID: 2019-06-26-1-1
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 07/03/2019
Date Tested: 07/03/2019
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke; OK Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
319915099150Bar BrokeFred
Temperature 72 F
UTM 400KIP

Test 2 of 3

DIME Test ID: 2019-06-26-1-2
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 07/03/2019
Date Tested: 07/03/2019
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke; OK Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
319616096160Bar BrokeFred
Temperature 72 F
UTM 400KIP

Test 3 of 3

DIME Test ID: 2019-06-26-1-3
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 07/03/2019
Date Tested: 07/03/2019
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke; OK Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
319800098000Bar BrokeFred
Temperature 72 F
UTM 400KIP