Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 210837 DEA: 080J0804 EFIS: 0800000283 COOP: 081625
QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-15-34.7/51.6
Work Description: (Alternative Delivery) DESIGN-BUILD OF THE INTERSTATE 15 EXPRESS LANES PROJECT
Location Description: Riverside County and SBD-15-0.0/1.3
Contractor Name: Skanska-Ames, Joint Venture
Contractor Address: 1801 California Avenue, Corona, CA 92881
Resident Engineer: Roy Fisher (reports) Structure Rep.: Roy Fisher
DIME Sample ID: 2019-03-14-13
TL Number from the TL Form: 35
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 03/14/2019
Date that the sample was received by the laboratory/organization performing the testing: 03/18/2019
The quantity of what the sample constitutes: 6
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 974-35
Structure unique identifier: north of parkridge ave
Structure name: north of parkridge ave
The fabricator/manufacturer/facility name: robertsons
The concrete mix design number: SC590B39
The truck number from where the sample was collected: 1637
The batch plant ticket number from where the sample was collected: 4292799
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: skanka ames
A detailed description of where the material sample was collected: 10cy
Where the material sample would have been placed if not sampled: north of parkridge ave
From Lot No.: Unknown
Bag Lot No.: Unknown
DIME Test ID: 2019-03-14-13-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 03/29/2019
Date Tested: 03/28/2019
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.46 in^2
|
Cross sectional area of cylinder 2
|
28.46 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
3870 psi
|
Average diameter of cylinder 1
|
6.02 in
|
Average diameter of cylinder 2
|
6.02 in
|
Compressive strength of cylinder 1
|
3871.4 psi
|
Compressive strength of cylinder 2
|
3858.7 psi
|
Maximum load on cylinder 1
|
110180 lb
|
Maximum load on cylinder 2
|
109820 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
14 days
|
DIME Test ID: 2019-03-14-13-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 04/05/2019
Date Tested: 04/04/2019
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.46 in^2
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
4330 psi
|
Average diameter of cylinder 1
|
6.02 in
|
Average diameter of cylinder 2
|
6.01 in
|
Compressive strength of cylinder 1
|
4322.9 psi
|
Compressive strength of cylinder 2
|
4346.8 psi
|
Maximum load on cylinder 1
|
123030 lb
|
Maximum load on cylinder 2
|
123320 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
21 days
|
DIME Test ID: 2019-03-14-13-3
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 04/15/2019
Date Tested: 04/11/2019
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.46 in^2
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
4680 psi
|
Average diameter of cylinder 1
|
6.02 in
|
Average diameter of cylinder 2
|
6.01 in
|
Compressive strength of cylinder 1
|
4700.6 psi
|
Compressive strength of cylinder 2
|
4664.4 psi
|
Maximum load on cylinder 1
|
133780 lb
|
Maximum load on cylinder 2
|
132330 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
28 days
|