Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 88888 DEA: SMTL-STOCK EFIS: SMTL-STOCK
QA Service Level:
DIST-CO-RTE-PM: 59---
Work Description: Special project for SMTL stock material. Object Code: 1025. J2 DEA: 912680.
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown
DIME Sample ID: 2019-02-27-1
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Sample Organization Contact: (916) 227-7071
Type of Sample: Acceptance
Type of Material: Cementitious
Sample Taken Date: 02/27/2019
Date that the sample was received by the laboratory/organization performing the testing: 01/14/2019
The quantity of what the sample constitutes: 1 Bucket
A brief description of the sample: Rapid Setting Cement
From where was the sample collected: Job Site
Laboratory sample identification: CM194901
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: CTS Rapid Set
DIME Test ID: 2019-02-27-1-1
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 05/11/2022
Date Tested: 03/15/2019
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no
|
Age of specimen
|
3 days
|
The amount of flow
|
112 %
|
The amount of water used
|
45.3 %
|
Compressive strength of 1st specimen
|
4768 psi
|
Compressive strength of 2nd specimen
|
4745 psi
|
Compressive strength of 3rd specimen
|
4831 psi
|
Average Compressive strength (to nearest 10 psi)
|
4780 psi
|
DIME Test ID: 2019-02-27-1-2
Test Method: CTM 553-1: Method for Testing Thermal Stability of Mortar Made with Hydraulic Cement
Verified Date: 05/11/2022
Date Tested: 03/15/2019
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Average of test specimens broken to nearest 50 kPa, 23 ± 1.7°C for 48h
|
5180 kPa
|
Average of test specimens broken to nearest 50 kPa, 50 ± 1°C for 48h
|
4970 kPa
|
Thermal stability ratio
|
96
|
DIME Test ID: 2019-02-27-1-3
Test Method: CTM 527-February 2014: Method of Test for Expansion in Water and Contraction in Air of Portland Cement Mortar
Verified Date: 05/11/2022
Date Tested: 03/25/2019
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Average change in length in water
|
0.00 %
|
Average change in length in air
|
0.01 %
|
DIME Test ID: 2019-02-27-1-4
Test Method: ASTM C1038-14b: Standard Test Method for Expansion of Hydraulic Cement Mortar Bars Stored in Water (Cement Mortar Bars)
Verified Date: 05/11/2022
Date Tested: 03/26/2019
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: An unrecoverable error was made taking measurements for Specimen C. To keep the final result correct, 0 is entered as the initial value and the final value is the average of the other three values.
Test Result Compliance:
Additional Comments When Verified:
Specimen A Initial measurement at 24 hours
|
0.2546 in
|
Specimen B Initial measurement at 24 hours
|
0.2578 in
|
Specimen C Initial measurement at 24 hours
|
0 in
|
Specimen D Initial measurement at 24 hours
|
0.2399 in
|
Specimen A Final measurement at 14 days
|
0.255 in
|
Specimen B Final measurement at 14 days
|
0.2583 in
|
Specimen C Final measurement at 14 days
|
0.00047 in
|
Specimen D Final measurement at 14 days
|
0.2404 in
|
The average length of change of the four specimens
|
0.047 %
|