REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
Brian Boal |
Date Reported: |
12/03/2018 |
|
Address: |
TL Number: |
Unknown |
||
City: |
||||
Project Name: Pier Retention |
||||
Prime Contractor: Kiewit/Manson, AJV |
||||
Sample Taken Date: |
11/05/2018 |
Mix Design: |
4E01C5SS |
|
Contractor: Unknown |
Location : In San Francisco and Alameda Counties on Yerba Buena Island and .4 miles west of Oakland Toll plaza |
|||
Structure unique identifier: Unknown |
||||
Structure name: YBI Observation Structure |
||||
Location of Pour: YBI Bridge Deck and RW3 |
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 6.03 | 28.56 | 144465 | 5058.3 | 1 |
2 | 6.02 | 28.46 | 141293 | 4964.6 | 1 |
DIME Test ID: 2018-11-05-6-1
Number of specimens: 2
Compressive strength (to nearest 10 psi): 5010
Age of specimen: 28 days
Certified By: Larry McCrum
*Subject to final inspection by the Resident Engineer. |
TL- Report of Laboratory Testing