Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 210735 DEA: 071193U4 EFIS: 0713000007
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-10-37.2/42.4
Work Description: CONSTRUCT HOV LANES, WIDEN BRIDGES, AND REALIGN RAMPS.
Location Description: IN LA COUNTY FROM CITRUS STREET IN WEST COVINA TO ROUTE 57 IN POMONA
Contractor Name: Guy F. Atkinson
Contractor Address: 18201 Von Karman Ave, Suite #800, IRVINE CA 92612
Resident Engineer: Rodolfo Cao Structure Rep.: David Win
DIME Sample ID: 2018-10-16-17
TL Number from the TL Form: v41016
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 10/16/2018
Date that the sample was received by the laboratory/organization performing the testing: 10/17/2018
The quantity of what the sample constitutes: 8
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 946-v41016
Structure unique identifier: kellogg ramp deck pour
Structure name: kellogg ramp deck pour
The fabricator/manufacturer/facility name: HOLIDAY upland
The concrete mix design number: 3C6FX301
The truck number from where the sample was collected: 275
The batch plant ticket number from where the sample was collected: 134402
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: ATKINSON
A detailed description of where the material sample was collected: 5 cy
Where the material sample would have been placed if not sampled: kellogg ramp deck pour
From Lot No.: Unknown
Bag Lot No.: Unknown
DIME Test ID: 2018-10-16-17-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 10/31/2018
Date Tested: 10/26/2018
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
4890 psi
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.00 in
|
Compressive strength of cylinder 1
|
4895.6 psi
|
Compressive strength of cylinder 2
|
4883.8 psi
|
Maximum load on cylinder 1
|
138400 lb
|
Maximum load on cylinder 2
|
138065 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
10 days
|
DIME Test ID: 2018-10-16-17-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 10/31/2018
Date Tested: 10/30/2018
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.37 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
5130 psi
|
Average diameter of cylinder 1
|
6.01 in
|
Average diameter of cylinder 2
|
6.00 in
|
Compressive strength of cylinder 1
|
5112.8 psi
|
Compressive strength of cylinder 2
|
5148.2 psi
|
Maximum load on cylinder 1
|
145050 lb
|
Maximum load on cylinder 2
|
145540 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
14 days
|
DIME Test ID: 2018-10-16-17-3
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 11/14/2018
Date Tested: 11/13/2018
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
5570 psi
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.00 in
|
Compressive strength of cylinder 1
|
5491.0 psi
|
Compressive strength of cylinder 2
|
5657.2 psi
|
Maximum load on cylinder 1
|
155230 lb
|
Maximum load on cylinder 2
|
159930 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Type of fracture pattern of cylinder 2
|
4
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
28 days
|
DIME Test ID: 2018-10-16-17-4
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 11/28/2018
Date Tested: 11/27/2018
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
6230 psi
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.00 in
|
Compressive strength of cylinder 1
|
6138.0 psi
|
Compressive strength of cylinder 2
|
6329.3 psi
|
Maximum load on cylinder 1
|
173520 lb
|
Maximum load on cylinder 2
|
178930 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
42 days
|