Project ID: 210837 DEA: 080J0804 EFIS: 0800000283 COOP: 081625
QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-15-34.7/51.6
Work Description: (Alternative Delivery) DESIGN-BUILD OF THE INTERSTATE 15 EXPRESS LANES PROJECT
Location Description: Riverside County and SBD-15-0.0/1.3
Contractor Name: Skanska-Ames, Joint Venture
Contractor Address: 1801 California Avenue, Corona, CA 92881
Resident Engineer: Roy Fisher (reports) Structure Rep.: Roy Fisher
DIME Sample ID: 2018-10-18-2
TL Number from the TL Form: 12
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 10/18/2018
Date that the sample was received by the laboratory/organization performing the testing: 10/22/2018
The quantity of what the sample constitutes: 6
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 974-12
Structure unique identifier: corona bridge footing abt2 footing cidhpiles
Structure name: corona bridge footing abt2 footing cidhpiles
The fabricator/manufacturer/facility name: robertsons
The concrete mix design number: RRM18087
The truck number from where the sample was collected: na
The batch plant ticket number from where the sample was collected: na
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: SKANSKA AMES
A detailed description of where the material sample was collected: load 1
Where the material sample would have been placed if not sampled: corona bridge footing abt2 footing cidhpiles
From Lot No.: Unknown
Bag Lot No.: Unknown
DIME Test ID: 2018-10-18-2-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 10/26/2018
Date Tested: 10/25/2018
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
2520 psi
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.00 in
|
Compressive strength of cylinder 1
|
2548.3 psi
|
Compressive strength of cylinder 2
|
2501.2 psi
|
Maximum load on cylinder 1
|
72040 lb
|
Maximum load on cylinder 2
|
70710 lb
|
Type of fracture pattern of cylinder 1
|
4
|
Type of fracture pattern of cylinder 2
|
4
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
7 days
|
DIME Test ID: 2018-10-18-2-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 11/02/2018
Date Tested: 11/01/2018
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
3140 psi
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.00 in
|
Compressive strength of cylinder 1
|
3187.1 psi
|
Compressive strength of cylinder 2
|
3098.3 psi
|
Maximum load on cylinder 1
|
90100 lb
|
Maximum load on cylinder 2
|
87590 lb
|
Type of fracture pattern of cylinder 1
|
4
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
14 days
|
DIME Test ID: 2018-10-18-2-3
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 11/16/2018
Date Tested: 11/15/2018
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
3870 psi
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.01 in
|
Compressive strength of cylinder 1
|
3928.5 psi
|
Compressive strength of cylinder 2
|
3818.5 psi
|
Maximum load on cylinder 1
|
111060 lb
|
Maximum load on cylinder 2
|
108330 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
28 days
|