Project Information

Project ID: 209695 DEA: 08347704 EFIS: 0800000616 QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-SR-58-0/12.9
Work Description: (Alternative Delivery) The CMGC project will upgrade SR 58 from 2- to 4-lanes in San Bernardino County from the Kern County line to 7.5 miles east of US-395.
Location Description: SR-58 / 395 Kramer Junction project. In San Bernardino County from the Kern County line to 7.5 miles east of US-395.
Contractor Name: KIEWIT INFRASTRUCTURE WEST CO.
Contractor Address: 2215 E 1ST STREET, VANCOUVER, WA 98661
Resident Engineer: Shaine Shahidi Structure Rep.: Osama Abdalla

Sample Information

DIME Sample ID: 2018-08-17-5
TL Number from the TL Form: 2-8-16-18
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 08/17/2018
Date that the sample was received by the laboratory/organization performing the testing: 08/20/2018
The quantity of what the sample constitutes: 2
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Manufacturer
Laboratory sample identification: 976-1718
Structure unique identifier: mix desing sample at 415am
Structure name: mix desing sample at 415am
The fabricator/manufacturer/facility name: keiwitt

Material Information

The concrete mix design number: lb18-0057
The truck number from where the sample was collected: 407
The batch plant ticket number from where the sample was collected: 2008
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: keiwiit
A detailed description of where the material sample was collected: at 1035 yard
Where the material sample would have been placed if not sampled: mix desing sample at 415am
From Lot No.: Unknown
Bag Lot No.: Unknown

Test Results

Test 1 of 1

DIME Test ID: 2018-08-17-5-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 08/29/2018
Date Tested: 08/24/2018
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test: Sample tested 8/24/18 @ 4:30AM
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 5.99 in
Average diameter of cylinder 2 5.97 in
Cross sectional area of cylinder 1 28.18 in^2
Cross sectional area of cylinder 2 27.99 in^2
Compressive strength (to nearest 10 psi) 430 psi
Maximum load on cylinder 1 11360 lb
Maximum load on cylinder 2 12560 lb
Compressive strength of cylinder 1 403.1 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 448.7 psi
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 7 days
Age of specimen in hours no data