Print Report | Back to Sample Detail

Sample Record for 2018-07-26-5

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 88888 DEA: SMTL-STOCK EFIS: SMTL-STOCK QA Service Level:
DIST-CO-RTE-PM: 59---
Work Description: Special project for SMTL stock material. Object Code: 1025. J2 DEA: 912680.
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2018-07-26-5
TL Number from the TL Form: Unknown
Sample Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Sample Organization Contact: (916) 227-7071
Type of Sample: Annual Source Testing
Type of Material: Cementitious
Sample Taken Date: 07/26/2018
Date that the sample was received by the laboratory/organization performing the testing: 07/26/2018
The quantity of what the sample constitutes: 1 Bucket
A brief description of the sample: Type I/II
From where was the sample collected: Source
Laboratory sample identification: CM185855
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Mountain Cement

Material Information

Brand: Mountain Cement
Mill: Laramie
Type of Cementitious Material: Type II Cement

Test Results

Test 1 of 6

DIME Test ID: 2018-07-26-5-2
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 03/22/2019
Date Tested: 09/07/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 3 Day Break -- Specimen 1 break was outside allowable range. Correct final result is 3460 PSI.
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Compressive strength of 1st specimen (psi) 3144 psi
Compressive strength of 2nd specimen (psi) 3477 psi
Compressive strength of 3rd specimen (psi) 3441 psi
Average Compressive strength (to nearest 10 psi) 3350 psi

Test 2 of 6

DIME Test ID: 2018-07-26-5-3
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 03/22/2019
Date Tested: 09/11/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 7 day Break
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Compressive strength of 1st specimen (psi) 4114 psi
Compressive strength of 2nd specimen (psi) 4019 psi
Compressive strength of 3rd specimen (psi) 4244 psi
Average Compressive strength (to nearest 10 psi) 4130 psi

Test 3 of 6

DIME Test ID: 2018-07-26-5-4
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 03/22/2019
Date Tested: 10/02/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 28 Day Break
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Compressive strength of 1st specimen (psi) 6094 psi
Compressive strength of 2nd specimen (psi) 5598 psi
Compressive strength of 3rd specimen (psi) 5675 psi
Average Compressive strength (to nearest 10 psi) 5790 psi

Test 4 of 6

DIME Test ID: 2018-07-26-5-5
Test Method: ASTM C185-15a: Standard Test Method for Air Content of Hydraulic Cement Mortar
Verified Date: 03/22/2019
Date Tested: 08/21/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Specific gravity 3.15
Water Content 246 mL
The amount of flow (In percent) 92 %
The amount of water used (In percent) 70.29 %
Net Weight of Sample 850.2 grams
Air Content 5 %

Test 5 of 6

DIME Test ID: 2018-07-26-5-6
Test Method: ASTM C191-13: Standard Test Methods for Time of Setting of Hydraulic Cement by Vicat Needle
Verified Date: 03/22/2019
Date Tested: 09/07/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Type of Water Used Type III grade reagent water
Initial time of setting 134 min
Final time of setting no data

Test 6 of 6

DIME Test ID: 2018-07-26-5-7
Test Method: ASTM C204-11: Standard Test Methods for Fineness of Hydraulic Cement by Air-Permeability Apparatus
Verified Date: 03/22/2019
Date Tested: 09/12/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Method Used Test Method A
Test Time 93 seconds
Fineness 3882 cm^2/g