Print Report | Back to Sample Detail

Sample Record for 2018-07-19-4

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 88888 DEA: SMTL-STOCK EFIS: SMTL-STOCK QA Service Level:
DIST-CO-RTE-PM: 59---
Work Description: Special project for SMTL stock material. Object Code: 1025. J2 DEA: 912680.
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2018-07-19-4
TL Number from the TL Form: Unknown
Sample Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Sample Organization Contact: (916) 227-7071
Type of Sample: Annual Source Testing
Type of Material: Cementitious
Sample Taken Date: 07/19/2018
Date that the sample was received by the laboratory/organization performing the testing: 07/19/2018
The quantity of what the sample constitutes: 1 Bucket
A brief description of the sample: Type II/V
From where was the sample collected: Source
Laboratory sample identification: CM185827
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Cal Portland

Material Information

Brand: Cal Portland
Mill: Mojave
Type of Cementitious Material: Type II/V Cement

Test Results

Test 1 of 6

DIME Test ID: 2018-07-19-4-2
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 01/18/2019
Date Tested: 08/16/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 3 Day Break
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Compressive strength of 1st specimen (psi) 3683 psi
Compressive strength of 2nd specimen (psi) 3714 psi
Compressive strength of 3rd specimen (psi) 3767 psi
Average Compressive strength (to nearest 10 psi) 3720 psi

Test 2 of 6

DIME Test ID: 2018-07-19-4-3
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 01/18/2019
Date Tested: 08/20/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 7 Day Break
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Compressive strength of 1st specimen (psi) 4502 psi
Compressive strength of 2nd specimen (psi) 4436 psi
Compressive strength of 3rd specimen (psi) 4466 psi
Average Compressive strength (to nearest 10 psi) 4470 psi

Test 3 of 6

DIME Test ID: 2018-07-19-4-4
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 01/18/2019
Date Tested: 09/10/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 28 Day Break
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Compressive strength of 1st specimen (psi) 5746 psi
Compressive strength of 2nd specimen (psi) 5649 psi
Compressive strength of 3rd specimen (psi) 5592 psi
Average Compressive strength (to nearest 10 psi) 5660 psi

Test 4 of 6

DIME Test ID: 2018-07-19-4-5
Test Method: ASTM C185-15a: Standard Test Method for Air Content of Hydraulic Cement Mortar
Verified Date: 01/18/2019
Date Tested: 08/21/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Specific gravity 3.15
Water Content 238
The amount of flow (In percent) 89 %
The amount of water used (In percent) 68.00 %
Net Weight of Sample 843.9 grams
Air Content 7 %

Test 5 of 6

DIME Test ID: 2018-07-19-4-6
Test Method: ASTM C191-13: Standard Test Methods for Time of Setting of Hydraulic Cement by Vicat Needle
Verified Date: 01/18/2019
Date Tested: 09/06/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Type of Water Used Type IV grade reagent water
Initial time of setting 155 min
Final time of setting no data

Test 6 of 6

DIME Test ID: 2018-07-19-4-7
Test Method: ASTM C204-11: Standard Test Methods for Fineness of Hydraulic Cement by Air-Permeability Apparatus
Verified Date: 01/18/2019
Date Tested: 07/27/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Method Used Test Method A
Test Time 109 seconds
Fineness 4203 cm^2/g