Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 213267 DEA: 04013584 EFIS: 0416000289
QA Service Level: 1
DIST-CO-RTE-PM: 04-SF-80-8.0/8.3,0.9/1.4
Work Description: Pier Retention
Location Description: In San Francisco and Alameda Counties on Yerba Buena Island and .4 miles west of Oakland Toll plaza
Contractor Name: Kiewit/Manson, AJV
Contractor Address: 4650 Business Center Drive, Fairfield,CA 94804
Resident Engineer: Brian Boal Structure Rep.: Unknown
DIME Sample ID: 2018-07-09-1
TL Number from the TL Form: Unknown
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Headed Bars
Sample Taken Date: 07/09/2018
Date that the sample was received by the laboratory/organization performing the testing: 07/12/2018
The quantity of what the sample constitutes: Unknown
A brief description of the sample: t.heads
From where was the sample collected: Source
Laboratory sample identification: Unknown
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: HRC
Production or Authorization Testing: Production Testing
Rebar Heat Number(s): 4073781
Head Manufacturer Lot Number(s): MM14103503
Rebar Size: 10
Headed Bar Model Name: HRC150
Size of Head: Reduced Size - 4x
Head Connection Type: Friction Weld
Head Shape: Circular
Rebar Manufacturer: CMC
Head Manufacturer: HRC
Head Fabricator: HRC
Material Standard Code: ASTM A706
Headed Bar Unique ID:
DIME Test ID: 2018-07-09-1-1
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 07/17/2018
Date Tested: 07/17/2018
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke; OK Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 1 | 1.27 | 124000 | 97640 | Bar Broke | Brian |
| |
Temperature
|
72 F
|
UTM
|
400KIP
|
DIME Test ID: 2018-07-09-1-2
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 07/17/2018
Date Tested: 07/17/2018
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke; OK Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 1 | 1.27 | 124090 | 97710 | Bar Broke | Brian |
| |
Temperature
|
72 F
|
UTM
|
400KIP
|
DIME Test ID: 2018-07-09-1-3
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 07/17/2018
Date Tested: 07/17/2018
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Head Popped Off
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 1 | 1.27 | 117460 | 92490 | Head Popped Off | Brian |
| |
Temperature
|
72 F
|
UTM
|
400KIP
|
DIME Test ID: 2018-07-09-1-4
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 07/17/2018
Date Tested: 07/17/2018
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Head Popped Off
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 1 | 1.27 | 122550 | 96500 | Head Popped Off | Brian |
| |
Temperature
|
72 F
|
UTM
|
400KIP
|