Project ID: 88888 DEA: SMTL-STOCK EFIS: SMTL-STOCK
QA Service Level:
DIST-CO-RTE-PM: 59---
Work Description: Special project for SMTL stock material. Object Code: 1025. J2 DEA: 912680.
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown
DIME Sample ID: 2018-06-11-2
TL Number from the TL Form: Unknown
Sample Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Sample Organization Contact: (916) 227-7071
Type of Sample: Annual Source Testing
Type of Material: Cementitious
Sample Taken Date: 06/11/2018
Date that the sample was received by the laboratory/organization performing the testing: 06/11/2018
The quantity of what the sample constitutes: 1 Bucket
A brief description of the sample: Type II/V
From where was the sample collected: Source
Laboratory sample identification: CM185863
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: LaFarge
DIME Test ID: 2018-06-11-2-2
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 08/03/2018
Date Tested: 06/21/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 3 Day Break
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no
|
Compressive strength of 1st specimen (psi)
|
2469 psi
|
Compressive strength of 2nd specimen (psi)
|
2522 psi
|
Compressive strength of 3rd specimen (psi)
|
2643 psi
|
Average Compressive strength (to nearest 10 psi)
|
2540 psi
|
DIME Test ID: 2018-06-11-2-3
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 08/03/2018
Date Tested: 06/25/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 7 Day Break
Test Result Compliance: complies
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no
|
Compressive strength of 1st specimen (psi)
|
3303 psi
|
Compressive strength of 2nd specimen (psi)
|
3040 psi
|
Compressive strength of 3rd specimen (psi)
|
3283 psi
|
Average Compressive strength (to nearest 10 psi)
|
3210 psi
|
DIME Test ID: 2018-06-11-2-4
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 08/03/2018
Date Tested: 07/16/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 28 Day Break
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no
|
Compressive strength of 1st specimen (psi)
|
4026 psi
|
Compressive strength of 2nd specimen (psi)
|
3971 psi
|
Compressive strength of 3rd specimen (psi)
|
4263 psi
|
Average Compressive strength (to nearest 10 psi)
|
4090 psi
|
DIME Test ID: 2018-06-11-2-5
Test Method: ASTM C185-15a: Standard Test Method for Air Content of Hydraulic Cement Mortar
Verified Date: 08/03/2018
Date Tested: 06/15/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Specific gravity
|
3.15
|
Water Content
|
230
|
The amount of flow (In percent)
|
82 %
|
The amount of water used (In percent)
|
65.71 %
|
Net Weight of Sample
|
834.4 grams
|
Air Content
|
8 %
|
DIME Test ID: 2018-06-11-2-6
Test Method: ASTM C191-13: Standard Test Methods for Time of Setting of Hydraulic Cement by Vicat Needle
Verified Date: 08/03/2018
Date Tested: 06/26/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Type of Water Used
|
Potable
|
Time in minutes of last penetration greater than 25mm (E)
|
109 min
|
Time in minutes of first penetration less than 25mm (H)
|
110 min
|
Penetration reading at time E
|
26 mm
|
Penetration reading at time H
|
25 mm
|
Initial time of setting
|
110 min
|
Final time of setting
|
no data
|
Method Used
|
Test Method A
|
DIME Test ID: 2018-06-11-2-7
Test Method: ASTM C204-11: Standard Test Methods for Fineness of Hydraulic Cement by Air-Permeability Apparatus
Verified Date: 08/03/2018
Date Tested: 07/23/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Method Used
|
Test Method A
|
Test Time
|
102 seconds
|
Fineness
|
4076 cm^2/g
|