Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 208945 DEA: 07288604 EFIS: 0700021080 COOP: 074663
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-710-6.0-9.4
Work Description: Gerald Desmond Bridge Replacement - A Design Build project. IQA samples will be selected by Port/Caltrans representatives and sent to Translab for testing.
Location Description: Port of Long Beach (District 7)
Contractor Name: Shimmick/FCC/Impregilo (SFI) JV
Contractor Address: 11 Golden Shore, Suite 330, Long Beach, CA 90802
Resident Engineer: Structure Rep.: Sami Deeb
DIME Sample ID: 2018-05-14-16
TL Number from the TL Form: 866-3218
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 05/14/2018
Date that the sample was received by the laboratory/organization performing the testing: 05/16/2018
The quantity of what the sample constitutes: 4
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 866-3218
Structure unique identifier: Unknown
Structure name: PRECAST BRIDGE DECK SLAB C1 NUMBER1
The fabricator/manufacturer/facility name: SFI LONG BEACH
The concrete mix design number: SFI LWSBS5
The truck number from where the sample was collected: 507
The batch plant ticket number from where the sample was collected: 427715
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: CHUTE FROM TRUCK
Where the material sample would have been placed if not sampled: LIGHT WEIGHT DECK SLAB C1 NUMBER 1
From Lot No.: Unknown
Bag Lot No.: Unknown
DIME Test ID: 2018-05-14-16-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521 Cured in accordance with ASTM C511
Verified Date: 08/06/2018
Date Tested: 08/06/2018
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.46 in^2
|
Cross sectional area of cylinder 2
|
28.56 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
8320 psi
|
Average diameter of cylinder 1
|
6.02 in
|
Average diameter of cylinder 2
|
6.03 in
|
Compressive strength of cylinder 1
|
8494.0 psi
|
Compressive strength of cylinder 2
|
8152.3 psi
|
Maximum load on cylinder 1
|
241740 lb
|
Maximum load on cylinder 2
|
232830 lb
|
Type of fracture pattern of cylinder 1
|
4
|
Type of fracture pattern of cylinder 2
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
84 days
|
DIME Test ID: 2018-05-14-16-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521 Cured in accordance with ASTM C511
Verified Date: 09/07/2018
Date Tested: 09/04/2018
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.46 in^2
|
Cross sectional area of cylinder 2
|
28.46 in^2
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Compressive strength (to nearest 10 psi)
|
8450 psi
|
Average diameter of cylinder 1
|
6.02 in
|
Average diameter of cylinder 2
|
6.02 in
|
Compressive strength of cylinder 1
|
8196.4 psi
|
Compressive strength of cylinder 2
|
8704.1 psi
|
Maximum load on cylinder 1
|
233270 lb
|
Maximum load on cylinder 2
|
247720 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
113 days
|