Print Report | Back to Sample Detail

Sample Record for 2018-05-10-7

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 209114 DEA: 040A7104 EFIS: 0400000160 COOP: 042550 QA Service Level: 1
DIST-CO-RTE-PM: 04-ALA-880-28.4/29.2
Work Description: WIDEN ROADS, RECONSTRUCT RAMPS WITH HMA, REPLACE 2 CONC OVERCROSSINGS.
Location Description: ALAMEDA COUNTY IN ALAMEDA AND OAKLAND FROM 0.2 MILE SOUTH OF 29TH AVENUE OVERCROSSING TO 0.3 MILE NORTH OF 23RD AVENUE OVERCROSSING.
Contractor Name: RGW Construction
Contractor Address: 550 GREENVILLE ROAD, LIVERMORE CA 94550
Resident Engineer: Joy Cheung Structure Rep.: Maxime Dabilly

Sample Information

DIME Sample ID: 2018-05-10-7
TL Number from the TL Form: C690174
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (530) 329-6527
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 05/10/2018
Date that the sample was received by the laboratory/organization performing the testing: 05/17/2018
The quantity of what the sample constitutes: 250
A brief description of the sample: 8 Rebar with Bartec Coupler
From where was the sample collected: Job Site
Laboratory sample identification: Unknown
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Unknown

Material Information

Production or Authorization Testing: Production Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: Nucor
Coupler Manufacturer: BarTec
Intermediate Assembler or Fabricator: Harris Rebar
Rebar Size: 8
Coupler Model: 8 Bartec Coupler
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter: Unknown
Rebar Hoop Fabricator: Unknown
Coupler Component Heat/Lot Number(s): DL12105782
Rebar Heat Number(s): 1202000412
Rebar Size 2 :
Coupler Unique ID:

Test Results

Test 1 of 3

DIME Test ID: 2018-05-10-7-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Verified Date: 05/21/2018
Date Tested: 05/18/2018
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 1
SampleMfg. Lot Number(s)SizeArea (sqin)Slip (inch)Peak Load (lbf)Peak Stress (psi)CommentsTested By
1C13#8/25mm0.79-0.00247245091709Service SpliceBrian
Temperature 72 F
UTM 400KIP
Halo ID Small

Test 2 of 3

DIME Test ID: 2018-05-10-7-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Verified Date: 05/21/2018
Date Tested: 05/18/2018
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 1
SampleMfg. Lot Number(s)SizeArea (sqin)Slip (inch)Peak Load (lbf)Peak Stress (psi)CommentsTested By
2C13#8/25mm0.7907389893542Service SpliceBrian
Temperature 72 F
UTM 400KIP
Halo ID Small

Test 3 of 3

DIME Test ID: 2018-05-10-7-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Verified Date: 05/21/2018
Date Tested: 05/18/2018
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 1
SampleMfg. Lot Number(s)SizeArea (sqin)Slip (inch)Peak Load (lbf)Peak Stress (psi)CommentsTested By
3C13#8/25mm0.7907402793705Service SpliceBrian
Temperature 72 F
UTM 400KIP
Halo ID Small