Project Information

Project ID: 211197 DEA: 072827U4 EFIS: 0714000204 QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-5,101-16.4,S0.0/25.9
Work Description: WIDEN SHOULDERS, INSTALL MIDWEST GUARDRAIL SYSTEM AND CRASH CUSHIONS.
Location Description: LOS ANGELES COUNTY IN LOS ANGELES AT VARIOUS LOCATIONS FROM ROUTE 5/60 SEPARATION TO 0.1 MILE WEST OF VENTURA BOULEVARD OVERCROSSING.
Contractor Name: PETERSON-CHASE GENERAL ENGINEERING CONSTRUCTION, INC.
Contractor Address: 16351 Construction Circle West, Irvine, CA 92606
Resident Engineer: Kris (Kalyanakrishnan) Venkataraman Structure Rep.: Dermegerdichian Ambaye

Sample Information

DIME Sample ID: 2018-04-25-16
TL Number from the TL Form: S LOC 47 1
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 04/25/2018
Date that the sample was received by the laboratory/organization performing the testing: 05/04/2018
The quantity of what the sample constitutes: 2
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 981-1
Structure unique identifier: AUSTIN VAULT 16 INCH CIDH SB 101 VAN BUYS ON RAMP
Structure name: AUSTIN VAULT 16 INCH CIDH SB 101 VAN BUYS ON RAMP
The fabricator/manufacturer/facility name: Associated Ready Mix

Material Information

The concrete mix design number: NOT PROVIDED
The truck number from where the sample was collected: 467
The batch plant ticket number from where the sample was collected: 5809746
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: PLANT
A detailed description of where the material sample was collected: TRUCK
Where the material sample would have been placed if not sampled: AUSTIN VAULT 16 INCH CIDH SB 101 VAN BUYS ON RAMP
From Lot No.: Unknown
Bag Lot No.: Unknown

Test Results

Test 1 of 1

DIME Test ID: 2018-04-25-16-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 05/23/2018
Date Tested: 05/23/2018
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 6.00 in
Average diameter of cylinder 2 6.00 in
Cross sectional area of cylinder 1 28.27 in^2
Cross sectional area of cylinder 2 28.27 in^2
Compressive strength (to nearest 10 psi) 4730 psi
Maximum load on cylinder 1 132430 lb
Maximum load on cylinder 2 135260 lb
Compressive strength of cylinder 1 4684.5 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 4784.6 psi
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 28 days
Age of specimen in hours no data