Print Report | Back to Sample Detail

Sample Record for 2017-12-16-1

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 209217 DEA: 080F5404 EFIS: 0800000136 COOP: 081468 QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-91,15-0.0/13.04, 35.64/45.14
Work Description: SR-91 Corridor Improvement Project: Develop approx. 8 miles of tolled express lanes and related improvements within SR 91 between the Riverside/Orange County line and I-15, including transition areas.
Location Description: 08-RIV-91-0.0/13.04; 12-ORA-91-R14.43/R18.91; 08-RIV-15-35.64/45.14
Contractor Name: Atkinson Walsh, Joint Venture
Contractor Address: 905 E 3rd St, Corona, CA 92879
Resident Engineer: Salim Khalil Structure Rep.: Alex Angha

Sample Information

DIME Sample ID: 2017-12-16-1
TL Number from the TL Form: SRL405
Sample Submitted By Organization: CT - Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 12/16/2017
Date that the sample was received by the laboratory/organization performing the testing: 12/16/2017
The quantity of what the sample constitutes: 6
A brief description of the sample: 6X12
From where was the sample collected: Job Site
Laboratory sample identification: 888-SRL405
Structure unique identifier: 91CIP
Structure name: 91 WB AT MAIN ST ON RAMP
The fabricator/manufacturer/facility name: Holliday Rock Chino

Material Information

The concrete mix design number: CM4261
The truck number from where the sample was collected: 684
The batch plant ticket number from where the sample was collected: 118066962
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: NP
Where the material sample would have been placed if not sampled: 91 WB AT MAIN ST ON RAMP
From Lot No.: Unknown
Bag Lot No.: Unknown

Test Results

Test 1 of 2

DIME Test ID: 2017-12-16-1-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 12/21/2017
Date Tested: 12/19/2017
Submitted By Organization: CT - Southern Regional Laboratory
Organization Address: 13970 Victoria St,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 213-792-4794
General Comments for this Test: PLEASE NOTE THIS IS 10 HOUR BREAK DIME IS NOT ALLOWING TO INPUT CYLINDER AGE AS HOURS
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 6.01 in
Average diameter of cylinder 2 6.01 in
Cross sectional area of cylinder 1 28.37 in^2
Cross sectional area of cylinder 2 28.37 in^2
Compressive strength (to nearest 10 psi) 3680 psi
Maximum load on cylinder 1 103560 lb
Maximum load on cylinder 2 104970 lb
Compressive strength of cylinder 1 3650.3 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 3700.0 psi
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 1 days
Age of specimen in hours no data

Test 2 of 2

DIME Test ID: 2017-12-16-1-2
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 12/26/2017
Date Tested: 12/26/2017
Submitted By Organization: CT - Southern Regional Laboratory
Organization Address: 13970 Victoria St,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 213-792-4794
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 4
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 6.01 in
Average diameter of cylinder 2 6.00 in
Average diameter of cylinder 3 6.00 in
Average diameter of cylinder 4 6.01 in
Cross sectional area of cylinder 1 28.37 in^2
Cross sectional area of cylinder 2 28.27 in^2
Cross sectional area of cylinder 3 28.27 in^2
Cross sectional area of cylinder 4 28.37 in^2
Compressive strength (to nearest 10 psi) 7920 psi
Maximum load on cylinder 1 231090 lb
Maximum load on cylinder 2 220160 lb
Maximum load on cylinder 3 220020 lb
Maximum load on cylinder 4 226040 lb
Compressive strength of cylinder 1 8145.6 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 7787.8 psi
Compressive strength of cylinder 3 7782.8 psi
Compressive strength of cylinder 4 7967.6 psi
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 3
Type of fracture pattern of cylinder 4 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Correction factor for cylinder 4 1
Age of specimen 10 days
Age of specimen in hours no data